2016-05-02 10:13:27FLORIDA ENERGY CODE
  
 REVISE ENERGY CALCULATIONS TO SHOW ACTUAL UNITS
 EXISTING OR INSTALLED.
 PROVIDE ORIGINAL SIGNATURES OF PREPARED AND OWNER/AGENT
 ON ENERGY CALCULATIONS.
  
 M1503.4 MAKEUP AIR REQUIRED.
 EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF
 400 CUBIC FEET PER MINUTE (0.19 M3/S) SHALL BE PROVIDED
 WITH MAKEUP AIR AT A RATE APPROXIMATELY EQUAL TO THE
 EXHAUST AIR RATE. SUCH MAKEUP AIR SYSTEMS SHALL BE
 EQUIPPED WITH A MEANS OF CLOSURE AND SHALL BE
 AUTOMATICALLY CONTROLLED TO START AND OPERATE
 SIMULTANEOUSLY WITH THE EXHAUST SYSTEM.
  
 PROVIDE MANUFACTURER SPECIFICATION FOR EQUIPMENT
 INSTALLED AT TIME OF INSPECTION.
  
  