| Plan Review Notes For Permit 16040430 |
| Permit Number |
16040430 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-19 10:19:53 | PLAN DENIED | | | 1) PROVIDE BATHROOM EXHAUST FOR GUEST AND | | | MASTER BATHROOM. PER TABLE M1507.4 | | | RESIDENTIAL CODE 2014 | | | 2) PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTIONS | | | FOR THE CLOTHES DRYER AND AIR CONDITIONING EQUIPMENT | | | WITH THE PLAN. PER SECTION M1502 CLOTHES DRYER EXHAUST. | | | 3) PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTIONS | | | ON THE KITCHEN HOOD WITH THE PLAN | | | PER SECTION M1503.4 MAKE UP AIR REQUIRED. | | | 4) REFER TO SECTION M1602.4 BALANCED RETURN AIR | | | EXCEPTION # 2 | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | | | | | | | |
|