Plan Review Notes
Plan Review Notes For Permit 16040429
Permit Number 16040429
Review Stop M
Sequence Number 2
Notes
Date Text
2016-05-16 14:31:202ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040429
 5/16/16
  
 1) M2: REFER TO SECTION C403.2.4.4 AND ADD MOTORZED
 OUTDOOR AIR DAMPERS TO THE ENERGY COMPLIANCE TABLE.
 2) SHEET M2.1 & S1.0: THE PLANS APPEAR TO SHOW THE NEW
 RTU ABUTTED TO THE PARAPET WALL WHICH CLOSE OFF THE
 REQUIRED MANUFACTURER'S CLEARANCE SPACE ON ONE SIDE OF
 THE UNIT.
 3) M2.1 & S1.0: THERE ARE CONFLICTING DETAILS FOR
 ATTACHING THE RTU AND RTU CURB ON THESE SHEETS. PLEASE
 PROVIDE CONSISTENT DETAILS ON THE PLANS, AND INCLUDE
 THE EXTERIOR DUCTWORK SUPPORT AND ANCHORAGE.
 4) THE PLAN DOESN'T INDICATE HOW AIR WILL BE RETURNED
 FROM THE OFFICE TO THE RTU- SEE SECTION 601.5.
 5) PROVIDE AN AIR DEVICE SCHEDULE
 6) THE RESPONSE FROM THE ARCHITECT TO COMMENT #5 FROM
 THE 1ST REVIEW STATES THAT THE MAKE UP AIR QUANTITY IS
 LESS THAN THE HVAC QUANTITY OF THE 5-TON SYSTEM,
 HOWEVER IT IS THE ADDED HEAT LOAD FROM THE MAKEUP AIR
 THAT MAY IMPACT THE SYSTEM. PLEASE REVISE THE AC
 CALCULATIONS TO SHOW THIS ADDITIONAL HEAT LOAD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  