| Plan Review Notes For Permit 16040429 |
| Permit Number |
16040429 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-05-16 14:31:20 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16040429 | | | 5/16/16 | | | | | | 1) M2: REFER TO SECTION C403.2.4.4 AND ADD MOTORZED | | | OUTDOOR AIR DAMPERS TO THE ENERGY COMPLIANCE TABLE. | | | 2) SHEET M2.1 & S1.0: THE PLANS APPEAR TO SHOW THE NEW | | | RTU ABUTTED TO THE PARAPET WALL WHICH CLOSE OFF THE | | | REQUIRED MANUFACTURER'S CLEARANCE SPACE ON ONE SIDE OF | | | THE UNIT. | | | 3) M2.1 & S1.0: THERE ARE CONFLICTING DETAILS FOR | | | ATTACHING THE RTU AND RTU CURB ON THESE SHEETS. PLEASE | | | PROVIDE CONSISTENT DETAILS ON THE PLANS, AND INCLUDE | | | THE EXTERIOR DUCTWORK SUPPORT AND ANCHORAGE. | | | 4) THE PLAN DOESN'T INDICATE HOW AIR WILL BE RETURNED | | | FROM THE OFFICE TO THE RTU- SEE SECTION 601.5. | | | 5) PROVIDE AN AIR DEVICE SCHEDULE | | | 6) THE RESPONSE FROM THE ARCHITECT TO COMMENT #5 FROM | | | THE 1ST REVIEW STATES THAT THE MAKE UP AIR QUANTITY IS | | | LESS THAN THE HVAC QUANTITY OF THE 5-TON SYSTEM, | | | HOWEVER IT IS THE ADDED HEAT LOAD FROM THE MAKEUP AIR | | | THAT MAY IMPACT THE SYSTEM. PLEASE REVISE THE AC | | | CALCULATIONS TO SHOW THIS ADDITIONAL HEAT LOAD. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|