Plan Review Notes
Plan Review Notes For Permit 16040429
Permit Number 16040429
Review Stop P
Sequence Number 1
Notes
Date Text
2016-04-22 14:51:31PLUMBING COMMENTS:
  
 1. GRAB BARS ARE TO BE MEASURED FROM THE TOP OF THE
 GRIPING SURFACE AT MIN 33IN 36IN MAX .
 PER FBC ACC. SEC. 609.4
  
 2. TOILET TO BE MEASURED FROM SIDE WALL 16IN MIN 18IN
 MAX.
 PER FBC ACC. SEC. 604.2
  
 3. PER FBC SEC. 306.2 THIS OCCUPANCY USE IS F-1 WHICH
 REQUIRES SEPARATE PLUMBING FACILITIES FOR MEN AND WOMEN
 PER FBC PL SEC. 403.2 THE EXCEPTION #3 DOES NOT APPLY
 BECAUSE THE PRIMARY USE IS F-1.
  
 4. A DRINKING FOUNTAIN IS REQUIRED PER FBC PL TABLE
 403.1
  
 5. PLEASE PROVIDE GREASE TRAP CALCULATIONS FROM SCHIER
 YOU CAN CONNECT LEE SCHNEEWEIS AT 800-538-4792.
 PER WPB AMEND. TO FBC 107.2.1
  
 6. SHOW LOCATION OF TOILET PAPER DISPENSER TO COMPLY
 WITH FBC ACC. SEC. 604.7
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  