2016-04-13 12:17:511ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040429
 4/13/16
  
 1) SHEET M1: THE VENTILATION FAN SCHEDULE INDICATES 560
 CFM CAPACITIES FOR TEF-1, AND EF-1: PLEASE CORRECT, AND
 INCLUDE THE CFM CAPACITY OF THE TEF-1 INTO THE AIR
 BALANCE CALCULATION AND SCHEDULE.
 2 ) PROVIDE A MECHANICAL ROOF PLAN INDICATING EQUIPMENT
 LOCATIONS, AND CLEARANCE DISTANCE MEASUREMENTS FOR AIR
 INTAKES AS REQUIRED IN SECTION 401.6, AND EXHAUST
 OUTLET TERMINATIONS AS REQUIRED IN SECTIONS 501.3.1 AND
 506.4.2 (TYPE II TERMINATIONS). PLEASE NOTE THAT THE
 HOOD EXHAUST OUTLET SHALL TERMINATE NOT LESS THAN 30
 INCHES ABOVE THE ROOF SURFACE (TO BE ADDRESSED UNDER
 HOOD PERMIT PLANS).
 3) REFER TO SECTIONS 304.11 FOR REQUIRED GUARDS AT ROOF
 EDGE IF NECESSARY, AND SECTION 306.5 FOR PERMANENT ROOF
 LADDER REQUIERMENTS IF NECESSARY AND NO COMPLIANT MEANS
 OF ACCESS EXISTS.
 3) SEPARATE PERMITS ARE REQUIRED FOR THE HOOD AND THE
 WALK-IN COOLER. PLEASE PLACE A NOTE ON THE PLANS TO
 CLARIFY AND PROVIDE DIRECTION.
 4) SHEET M3: PROVIDE THE WIND LOAD DESIGN CRITERIA ON
 THE PLANS FOR ANCHORAGE OF THE RTU, CURBS, AND FANS TO
 THE ROOF STRUCTURE- SEE SECTIONS 301.15 FBC-14
 MECHANCIAL, AND SECTION 1609 FBC-14 BUILDING. PLEASE
 PROVIDE COMPLETE DETAILS FOR INSTALLATION OF THE ROOF
 TOP FANS INCLUDING THE TYPE AND SIZE OF FASTENERS FOR
 MOUNTING THE CURBS TO THE STRUCTURE, AND THE FANS TO
 THE CURBS,
 5) REFER TO SECTION 508.1.1 AND INDICATE COMPLIANCE FOR
 MAKEUP AIR TEMPERATURE FOR THE PROPOSED HOOD SYSTEM (TO
 BE ADDRESSED UNDER HOOD PERMIT PLANS).
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
 6) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE NEW RTU-
 TYPE AND SIZE OF CONDENSATE PIPING, PIPING RUN AND
 DISCHARGE LOCATION, PIPING PRIOTECTION FROM UV
 DEGRADATION- SEE SECTION 307.
 7) THE $15,000 JOB VALUE LISTED ON THE APPLICATION
 APPEARS TOO LOW FOR THE SCOPE OF THE PROJECT. PLEASE
 PROVIDE AN ACCURATE VALUE BASED ON COSTS FOR LABOR,
 MATERIALS, EQUIPMENT, FIXTURES, AND DESIGN FEES-
 SECTION 109.3 WPB AMENDMENTS TO THE FLORIDA BUILDING
 CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  