| Date |
Text |
| 2016-04-11 15:32:30 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1. SHEET A 2- INDICATES TWO DOORS OPENING INTO THE EXIT |
| | CORRIDOR. DOOR 02- TOILET & DOOR 03 - OFFICE. |
| | |
| | PER NFPA 101 CHAPTER 7, MEANS OF EGRESS |
| | 7.2.1.4.3 DOOR LEAF ENCROACHMENT |
| | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE |
| | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, |
| | OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT |
| | MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A |
| | CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, |
| | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| | EXISTING BUILDING. |
| | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS |
| | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED |
| | WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY |
| | OPEN. |
| | |
| | PLEASE PROVIDE FOR THE DOORS TO SWING IN/AWAY FROM THE |
| | CORRIDOR OR PROVIDE MORE DETAILED INFORMATION |
| | INDICATING COMPLIANCE WITH THE ABOVE NOTED CODE. |
| | |
| | 2. SHEET E 1 - PLEASE PROVIDE FOR AN EXIT LIGHT TO BE |
| | INSTALLED AT THE FRONT AREA OF THE HALL/CORRIDOR |
| | PROVIDE FOR ILLUMINATION AND DIRECTION FROM EACH |
| | DIRECTION. |
| | |
| | 3. SHEET M 2 - PLEASE PROVIDE DETAILS AS TO THE MENU |
| | ITEMS AND FOOD PREPARATIONS INDICATING THAT GREASE |
| | LADEN VAPORS ARE NOT BEING PRODUCED AND THE TYPE OF |
| | HOOD VENTILATION PER NFPA 96. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |