2016-04-15 09:02:57INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. SHOW WINDOW RECEPTACLE REQUIRED, SHOW ON FLOOR PLAN
 AND PANEL SCHEDULE NEC 210.62 FBC 107.3.5
 2. PROVIDE A GENERAL NOTE INDICATING LOW VOLTAGE AND
 HOOD SUPPRESSION SYSTEMS TO BE PERMITTED SEPARATELY.
 FBC 107.3.5
 3. SHOW ON FLOOR PLAN THE EXIT LIGHT PER FIRE COMMENTS.
 FBC 107.3.5
 4. NOTE THAT 2ND SET OF PLANS ARE MISSING ELECTRICAL
 SHEETS
 5. PROVIDE NOTES TO INDICATE NEC 230.3 E FOR ID OF
 MULTIPLE SERVICES. LABEL 1 OF 2 AND 2 OF 2 ETC.
 6. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  