| 2016-04-15 09:02:57 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. SHOW WINDOW RECEPTACLE REQUIRED, SHOW ON FLOOR PLAN | | | AND PANEL SCHEDULE NEC 210.62 FBC 107.3.5 | | | 2. PROVIDE A GENERAL NOTE INDICATING LOW VOLTAGE AND | | | HOOD SUPPRESSION SYSTEMS TO BE PERMITTED SEPARATELY. | | | FBC 107.3.5 | | | 3. SHOW ON FLOOR PLAN THE EXIT LIGHT PER FIRE COMMENTS. | | | FBC 107.3.5 | | | 4. NOTE THAT 2ND SET OF PLANS ARE MISSING ELECTRICAL | | | SHEETS | | | 5. PROVIDE NOTES TO INDICATE NEC 230.3 E FOR ID OF | | | MULTIPLE SERVICES. LABEL 1 OF 2 AND 2 OF 2 ETC. | | | 6. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | | QUESTIONS REGARDING THIS PROJECT. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | |
|