Plan Review Notes
Plan Review Notes For Permit 16040429
Permit Number 16040429
Review Stop B
Sequence Number 1
Notes
Date Text
2016-04-18 08:02:51BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16040429
 ADD: 5505 S. DIXIE HWY. SUITE # 04
 CONT: TBD
 TEL: 561-856-6655
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. APRIL 18/2016
 ACTION: DENIED
  
 1) THE STATED VALUE OF THIS PERMIT IS EXTREMLY LOW. W P
 B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT FEES. ON
 BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL AND
 PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A
 FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) SHEET A-1 NOTATION # 8 INDICATES THE TENANT
 SEPARATION WALLS ARE TO BE 1 HOUR RATED. THE PLANS DO
 NOT PROVIDE A UL LISTING OR GYPSUM FIRE LISTING NOR
 DETAIL FOR THE INFILE WALL FOR DOOR BEING REMOVED. 2014
 FBC-B 708.3. & 708.4.
  
 3) THE SHEET A-1 INDICATES A CORRIDOR 4FEET WIDE AND 3
 FOOT DOORS SWINGING INTO THE CORRIDOR. PLEASE PROVIDE
 COMPLIANCE WITH
 2014 FBC-B 1005.7.1 DOORS. DOORS, WHEN FULLY OPENED,
 SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE THAN 7
 INCHES (178 MM). DOORS IN ANY POSITION SHALL NOT REDUCE
 THE REQUIRED WIDTH BY MORE THAN ONE-HALF.
  
 4) SHEET A-1 SHOWS THE DOOR E A EXISTING DOOR IN A 1
 HOUR TENANT SEPARATION WALL, PLEASE PROVIDE THE RATING
 ON THIS DOOR, SEE 2014 FBC-B TABLE 716.5.
  
 5) SHEET A-1 INDICATES THE RESTROOM TO BE 7 FEET IN
 LENGTH. SHEET A2 SHOWS A DETAIL OF THE RESTROOM. THE
 DETAIL ONLY SHOWS 4 FOOT 8 INCHES FROM THE EDGE OF THE
 LAVATORY OVER THE WATER CLOSET TO THE OPPOSITE WALL.
 PLEASE SHOW COMPLIANCE WITH 2014 FBC-ACCESS. CODE
 SECTION 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET
 SHALL BE 60 INCHES (1525 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES (1420
 MM) MINIMUM MEASURED PERPENDICULAR FROM THE REAR WALL.
  
 6) SHEET A2 DETAIL FOR HANDICAPPED FIXTURES AND
 ACCESSORIES SHOWS THE GRAB BARS BEING MEASURED FROM THE
 CENTER LINE TO FINISH FLOOR. PLEASE REVIEW 2014
 FBC-ACCESS. CODE SECTION 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, EXCEPT THAT AT WATER CLOSETS FOR
 CHILDREN?S USE COMPLYING WITH 604.9, GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION 18 INCHES (455 MM)
 MINIMUM AND 27 INCHES (685 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE.
  
 7) THERE IS NO MENTION IN THE ARCHITECTURAL SHEETS OF
 NEW HOLES CUT IN THE ROOF DECK, NO STRUCTURAL SHEETS,
 SHEET M2 SHOWS
 A NEW ROOF TOP EXHAUST FAN AND ROOF TOP RTU UNIT. SHEET
 M3 SHOWS A CUT SECTION THROUGH EACH OF THESE OPENINGS,
 THERE IS NO MENTION OF ANY BRACING THAT IS NECEASSRY
 FOR THE NEW OPENINGS. 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 8) THERE IS NO WIND DESIGN CRITERIA AS TO WHAT WIND
 SPEED, OR EXPOSURE THE ANCHORING SCHEDULE WAS DESIGNED
 FOR?
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS
  
 9) MISSING PRODUCT APPROVALS. 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: (31)(D)
 ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS, INTAKE
 AND EXHAUST FANS.
  
 10) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 11) PROVIDE COMPLIANCE WITH: 2014 FBC-B 1013.6
 MECHANICAL EQUIPMENT. GUARDS SHALL BE PROVIDED WHERE
 APPLIANCES, EQUIPMENT, FANS, ROOF HATCH OPENINGS OR
 OTHER COMPONENTS THAT REQUIRE SERVICE ARE LOCATED
 WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF
 A WALKING SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED
 MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR
 GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO
 PREVENT THE PASSAGE OF A SPHERE 21 INCHES (533 MM) IN
 DIAMETER. THE GUARD SHALL EXTEND NOT LESS THAN 30
 INCHES (762 MM) BEYOND EACH END OF SUCH APPLIANCE,
 EQUIPMENT, FAN OR COMPONENT.
  
 12) PROVIDE COMPLIANCE WITH: 2014 FBC-B 1013.7 ROOF
 ACCESS. GUARDS SHALL BE PROVIDED WHERE THE ROOF HATCH
 OPENING IS LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF
 EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR
 OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762 MM) ABOVE
 THE FLOOR, ROOF OR GRADE BELOW. THE GUARD SHALL BE
 CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21
 INCHES (533 MM) IN DIAMETER.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER