| Date |
Text |
| 2016-08-04 10:36:09 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: FRESENIUS MEDICAL CARE ADDITION |
| | JOB ADDRESS: 1522 & 1600 N. DIXIE HWY. |
| | DESCRIPTION: RENOVATION OF EXISTING SPACE |
| | MASTER PERMIT:16040415 |
| | REVISION: (THIS PACKET IS RUNNING TOGETHER WITH PERMIT |
| | 16040412) |
| | |
| | THE BELOW MENTIONED COMMENTS WILL RELATE TO BOTH |
| | PERMITS AS THEY ARE SHARING A SUBMITTAL |
| | 1. THERE ARE TWO SEPARATE PERMITS AND THEREFORE THERE |
| | SHOULD BE TWO SEPARATE PLAN SETS. IF NOT AT A MINIMUM |
| | THREE SETS SO THAT ONE CAN BE STORED ON RECORD FOR EACH |
| | PERMIT NUMBER EVEN IF THEY WILL BE SHARING THE JOB |
| | COPY. AT PRESENT THERE IS ONLY ONE SET OF DRAWINGS |
| | ATTACHED TO EACH PERMIT AND THEY DO NOT MATCH. THE |
| | SHEET INDEX OF T1.0 FOR EACH SET MENTIONS 11 |
| | INDIVIDUALLY NUMBERED ELECTRICAL SHEETS. THE SET OF |
| | PERMIT 16040415 IS MISSING SHEET E2.0A AND SHEET E2.2 |
| | IS REPLACED W/SHEET E2.2A. THE SET OF PERMIT 16040412 |
| | DOES INCLUDE SHEET E2.0A BUT ALSO HAS A SHEET E2.2A |
| | RATHER THAN AN E2.2. CORRECT THAT ACCORDINGLY. |
| | 2. YOU DID NOT RESPOND TO MY COMMENT #3 WHICH ADDRESSES |
| | THE DAYLIGHT ZONE ISSUE. I INADVERTENTLY CALLED OUT |
| | SHEET E2.1 WHICH OBVIOUSLY DOES NOT INCLUDE THE |
| | LIGHTING. IT IS SHEET E2.0A THAT ADDRESSES THE LIGHTING |
| | AND NOTHING HAS BEEN DONE TO ADDRESS THE DAYLIGHT |
| | LIGHTING ZONE CONTROL. PLEASE CORRECT THAT ACCORDINGLY. |
| | 3. WITH REGARDS TO MY COMMENT #4, THE FACT THAT THESE |
| | TWO BUILDINGS ARE TO BE CONNECTED WILL POSE A LIFE |
| | SAFETY HAZARD BY HAVING TWO SERVICES. THEREFORE, RATHER |
| | THAN HAVING SHUNT TRIP CAPABILITIES YOU SHALL PLACE A |
| | WARNING PLACARD AT EACH SERVICE INFORMING EMERGENCY |
| | PERSONNEL OF THE OTHER SERVICE AND THE LOCATION OF THE |
| | DISCONNECT. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |