| Date |
Text |
| 2016-04-14 12:46:58 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #16040415 |
| | 4/14/16 |
| | |
| | 1) SHEET M1.0: THE OUTSIDE AIR CALULATIONS ARE BASED ON |
| | THE OUTDATED FMC- 2010. THE CURRENT CODE IN EFFECT IS |
| | THE FBC- 2014 MECHANICAL: PLEASE REVIEW AND UPDATE. |
| | 2) M1.0: PLEASE INDICATE THE OFFICE OR ROOM NUMBERS IN |
| | THE OUTSIDE AIR SCHEDULE AND INCLUDE CALULATIONS FOR |
| | ALL ROOMS AND SPACES INCLUDING THE EXAMINATION AND |
| | MEDICAL PROCEDURE ROOMS- SEE TABLE 403.3. PLEASE NOTE |
| | THAT THE "WATER TREATMENT STORAGE" ROOMS LISTED IN THE |
| | CALCULATIONS DO NOT APPEAR TO BE IN THE SCOPE OF WORK |
| | FOR THIS PROJECT: PLEASE CLARIFY. |
| | 3) M1.0: PROVIDE EXHAUST VENTILATION CALCULATIONS FOR |
| | THE SOILED UTILITY, MED WASTE, AND LAB PREP ROOMS. |
| | PLEASE NOTE THAT NO EXHAUST HAS BEEN PROVIDED FOR THE |
| | LAB PREP ROOM- SEE TABLE 403.3 AND CLARIFY IF THERE IS |
| | LAB WORK OR CHEMICAL STORAGE IN THE THIS ROOM- SEE |
| | TABLE 6-4 ASHRAE 62.1-2010. |
| | 4) D1.0: PLEASE PROVIDE A SCOPE OF WORK FOR MECHANICAL |
| | DEMOLITION WITH CORREPONDING DRAWINGS AND DETAILS. |
| | 5) M-2.0A: THE 10" FLEX DUCTS SUPPLYING 405 CFMS EACH |
| | TO THE CONFERENCE ROOM ARE UNDERSIZED PER ACCA MANUAL D |
| | SIZING METHODS FOR LOW PRESSURE SYSTEMS. |
| | 6) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS |
| | OF ALL ROOF TOP EQUIPMENT- RTU'S, EXHAUST FANS, AIR |
| | INTAKES ETC- SEE SECTIONS 401.5 AND 501.3.1 FOR |
| | REQUIRED CLEARANCE DISTANCES AND PLACE MEASUREMENTS ON |
| | THE PLAN TO VERIFY COMPLIANCE. SUBMIT NOA'S OR FL. |
| | PRODUCT APPROVALS FOR THE ROOF TOP FANS, AND FAN AND |
| | RTU CURBS REVIEWED AND APPROVED WITH SIGNATURE BY THE |
| | EOR. PLEASE NOTE THAT GUARDS WILL BE REQUIRED FOR ALL |
| | SERVICEABLE EQUIPMENT ON THE ROOF WITHIN 10' OF A ROOF |
| | EDGE I.E. EF-6. |
| | 7) INDICATE THE USE OF EF-6 ON THE PLAN AND PROVIDE |
| | EXHAUST VENTILATION CALCULATIONS, MAKE-UP AIR, A |
| | VENTING DIAGRAM, AND MANUFACTURER'S SPECIFICATIONS FOR |
| | THE EXHAUST FAN AND DUCT WORK. |
| | 8) M-3.1: REFER TO SECTRION 301.15 AND PROVIDE WIND |
| | LOAD DESIGN CRITERIA AND COMPLETE ENGINEERED DETAILS |
| | FOR TIE DOWN OF THE RTUS, FANS, AND CURBS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |