| 2016-04-13 18:56:05 | THIS PERMIT IS RIDING ALONG WITH16040412 AND ARE |
| | SHARING THE PLANS, THEREFORE THE COMMENTS ARE COMMON TO |
| | BOTH PERMIT. |
| | |
| | ELECTRICAL REVIEW COMMENTS |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION OF THE FBC 2014 & NFPA 70 (NEC) 2011 |
| | EDITION |
| | |
| | CORRECTIONS REQUIRED: |
| | BLDG. DEPT. NOTES ON COVER SHEET |
| | 1. A) INDICATE THAT THE PLANS WERE DESIGNED TO MEET THE |
| | REQUIREMENTS OF THE 2008 NEC. D) REFERS TO THE LATEST |
| | CODE. THE 2011 EDITION OF THE NEC IS THE ONE CURRENTLY |
| | ADOPTED BUT IT IS NOT THE LATEST EDITION. |
| | SHEET E2.0A |
| | 1. NOTE 14 AGAIN REFERS TO AN OLD CODE. THOUGH THE |
| | VERBIAGE OF THE OLD CODE DIDN'T VARY WITH THE NEW ONE |
| | THE REFERENCE IS INCORRECT. |
| | 2. FROM THIS DRAWING IT IS VERY DIFFICULT TO RECOGNIZE |
| | WHAT AND WHERE WOULD THE DAYLIGHT ZONE BE FOR |
| | COMPLIANCE WITH THE FBC-EC402 & 405 |
| | SHEET E2.1A |
| | 1. NEC 225.34 RESTRICTS THE NUMBER OF DISCONNECTS AND |
| | REQUIRES THAT THEY BE GROUPED. |
| | SHEET E2.1B |
| | 1. PANELS LA & LB DO NOT COMPLY WITH NEC 110.26 |
| | SHEET E2.2A |
| | 1. SEPARATE PERMIT AND SUBMITTAL REQUIRED FOR THE FIRE |
| | ALARM. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |