| Notes |
| Date |
Text |
| 2016-04-19 13:49:08 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. REVISE THE FLOOR PLAN TO PROVIDE THE FOLLOWING | | | INFORMATION: WINDOW TYPE IN EACH OPENING, ROOM | | | DESIGNATIONS. FBC 107, PLAN SHOULD BE CLEAR AS TO | | | SCOPE. TWO DIFFERENT WINDOW PRODUCT APPROVALS PROVIDED, | | | ONE IMPACT AND ONE NON IMPACT, AND A MULLION PRODUCT | | | APPROVAL. FLOOR PLAN APPEARS TO SHOW A WINDOW AND A | | | DOOR. REVISE FLOOR PLAN TO SHOW PROPOSED INSTALLATION, | | | SIZES OF INDIVIDUAL WINDOWS, MULLION SPAN. SCOPE IS NOT | | | ADEQUATELY SHOWN. | | | | | | 2. FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN | | | HEIGHT, NOTE EXISTING CONDITIONS (TYPE OF WINDOW) AND | | | OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 704.1. THE | | | CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%. | | | | | | | | | | | | |
|