| Plan Review Notes For Permit 16040401 |
| Permit Number |
16040401 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-13 09:16:43 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | | | | | | | - ADD THE FOLLOWING ELECTRICAL NOTES | | | | | | 1 NEC 210.12 B AFCI PROTECTION | | | 2 NEC 406.11 TAMPER RESISTANT RECEPTACLES | | | 3 NEC 314.27 PADDLE FANS ( 70 POUND RATED BOX. ) | | | | | | - SMOKE ALARMS REQUIRED PER RESIDENTIAL CODE SECTIONS | | | 314 & 315 | | | - RECESSED LIGHTS SHALL BE 75 % HIGH EFFICIENT AS WELL | | | AS IC RATED AND SEALED TO NOT COMPROMISE THE BUILDING | | | THERMAL ENVELOPE. ( 2 CFM ) | | | - PROVIDE EXISTING RISER DIAGRAM WITH CONDUIT AND WIRE | | | SIZES, GROUNDING DETAIL , A PANEL SCHEDULE SHOWING | | | OVERCURRENT PROTECTION INFORMATION. |
|