| Plan Review Notes For Permit 16040401 |
| Permit Number |
16040401 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-03 09:15:20 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- EXISTING FLOOR PLAN SHOWS SINGLE ENTRY DOOR WITH 2 | | | SIDELITES. THE WIDOW AND DOOR SCHEDULE SHOWS A 5'0" X | | | 6'8" DOUBLE DOOR. THIS WILL REDUCE THE SIZE OF THE | | | EGRESS DOOR. NEED TO HAVE AT LEST 32" CLEAR OPENING ON | | | ONE DOOR LEAF. THEREFORE, THE PROPOSED DOUBLE DOOR | | | DOESN'T COMPLY. REVISE AS REQUIRED. SEC. 704 | | | FBC-EXISTING BUILDING, 5TH EDITION (2014). | | | | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: | | | A) EXTERIOR DOOR #5 BY THE DINING AREA. NOTE: SEE SIZE | | | SPECIFIED ON THE DOOR SCHEDULE. | | | | | | B) ENTRY DOOR WITH TRANSOM ASSEMBLY AS SPECIFIED ON | | | PLANS. NOTE: COORDINATE WITH ITEM #1 ABOVE. | | | | | | 3- ENGINEER TO REVIEW AND APPROVE ABOVE PRODUCT | | | APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY | | | AMENDMENTS. | | | | | | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] | | | | | | |
|