2016-04-14 15:41:591ST REVIEW 4/14/16
 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 - PROVIDE MANUFACTURE SPECS ON POOL EQUIPMENT SUCH AS
 LIGHTS, PUMPS, HEATER, CHLORINATER AND ETC, FURTHERMORE
 SHOW ELECTRIC SERVICE RISER WITH WIRE SIZES, CONDUIT
 DETAIL AND GROUNDING DETAIL. COMPLETE LOAD
 CALCULATIONS, PANEL SCHEDULES. WPBA 107
  
 - ADD A EQUIPOTENTIAL BONDING DETAIL WHICH IS MISSING
 ON DETAIL SHEET. ( MAKE SURE IT TIES IN ALL ELECTRTICAL
 COMPONENTS RELATED TO THE POOL ) NEC 680.26
  
 - IF A NON METALLIC RACEWAY IS BEING USED FOR THE UNDER
 WATER LUMINARE A # 8 AWG INSULATED GROUNDING CONDUCTOR
 SHALL BE ROUTED AND TERMINATED AT THE SHELL , J-BOX,
 TRANSFORMER PLUS A LISTED POTTING COMPOUND WILL PROTECT
 THE CONNECTION FROM POSSIBLE DETERIOATING EFFECT. NEC
 680.23 2B
  
 - GFCI PROTECTION REQUIRED FOR POOL PUMPS NEC 680.21 C
 , RECEPTACLES LOCATED WITHIN 20 FT OF THE INSIDE WALL
 OF THE POOL NEC 680.22 4 , LIGHTING WITHIN AND EXCEPT
 CLEARANCES STATED IN NEC 680.22 B 4