2016-04-12 08:36:35NFPA 13-8.6.5.3.5 SPRINKLERS INSTALLED UNDER OPEN
 GRATINGS SHALL BE OF THE INTERMEDIATE LEVEL/RACK
 STORAGE TYPE OR OTHERWISE SHIELDED FROM THE DISCHARGE
 OF OVERHEAD SPRINKLERS.
 NFPA 13-6.2.8 SPRINKLERS SUBJECT TO MECHANICAL INJURY
 SHALL BE PROTECTED WITH LISTED GUARDS.