| Plan Review Notes For Permit 16040380 |
| Permit Number |
16040380 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-12 08:36:35 | NFPA 13-8.6.5.3.5 SPRINKLERS INSTALLED UNDER OPEN | | | GRATINGS SHALL BE OF THE INTERMEDIATE LEVEL/RACK | | | STORAGE TYPE OR OTHERWISE SHIELDED FROM THE DISCHARGE | | | OF OVERHEAD SPRINKLERS. | | | NFPA 13-6.2.8 SPRINKLERS SUBJECT TO MECHANICAL INJURY | | | SHALL BE PROTECTED WITH LISTED GUARDS. |
|