Plan Review Notes
Plan Review Notes For Permit 16040372
Permit Number 16040372
Review Stop P
Sequence Number 2
Notes
Date Text
2016-07-12 06:16:131)THE PLAN REVIEW COMMENTS FROM THE REVIEW DONE ON
 5/9/16 HAVE NOT BEEN ADEQUATELY ADDRESSED.COMPLY WITH
 ALL PREVIOUS REVIEW COMMENTS.
 2) THE DRINKING FOUNTAINS SHALL COMPLY WITH THE 2014
 FL. ACCESSIBILITY CODE SEC.211.2 AND SECS.602.1THROUGH
 602.6 AND 602.7 AND FIGURE 602.5. SUBMIT MANUFACTURER'S
 SPECIFICATION SHEETS FOR THE UNIT. THE DETAIL ON SHT.
 T3.2 DOES NOT SHOW COMPLIANCE WITH THE CITED CODE
 SECTIONS. BOTH UNITS APPEAR TO BE AT THE SAME
 ELEVATION.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved