Plan Review Notes
Plan Review Notes For Permit 16040307
Permit Number 16040307
Review Stop P
Sequence Number 1
Notes
Date Text
2016-04-20 16:05:571ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT. A2.1A + SHT. P-2 EQUIPMENT LIST L14 + L15 DO
 NOT SHOW ANY PLUMBING REQUIREMENTS THEY ARE SHOWN ON
 PLUMBING DOES ANY OTHER EQUIPMENT REQUIRE PLUMBING.
 PLEASE CLARIFY PER WPB AMEND. TO FBC SEC. 107.2.1
  
 2. TOILET PAPER HOLER SHALL COMPLY WITH ALL DEMINSIONS
 OF FBC ACCC.SEC 604.7
  
 3. SHT. P2 EQUIPMENT LIST SHOWS A 2IN. DRAIN FOR L5 IT
 IS NOT SHOWN ON SANITARY RISER.
 PLEASE CLARIFY PER WPB AMEND. TO FBC SEC. 107.2.1
  
 4. A SERVICE SINK IS REQUIRED PER FBC PL TABLE 403.1
  
 5. SHT. A1.0 THE NOTE ON THE PLAN INDICATES 2 ADA
 UNISEX BATHROOMS SEPARATE FACILITIES ARE REQUIRED PER
 FBC PL SEC. 403.2
 PLEASE INDICATE ON ALL SHEETS MEN'S OR WOMEN'S BATHROOM
 WPB AMEND. TO FBC SEC. 107.2.1
  
 6. WHERE ARE THE CHEMICALS USED IN THIS LAB BING
 DISPOSED OF.
 PER WPB AMEND. TO FBC SEC. 107.2.1
  
 7. PLEASE PROVIDE MSDS SHEETS ON ALL CHEMICALS USED AND
 A REPORT CONTAINING A LISTING OF ALL CHEMICALS, THE
 AMOUNTS , THE STATE, WHAT TYPE OF CONTAINER THEY ARE
 STORED IN.
 PER WPB AMEND. TO FBC SEC. 107.2.1
  
 DO TO PLANS BEING INCOMPLETE OR UNCLEAR, A
 COMPREHENSIVE PLAN REVIEW CANNOT BE DONE AT THIS TIME,
 THERE MAYBE ADDITIONAL COMMENTS ON RESUBMITTAL OF
 PLANS.
  
  
  