2016-04-11 09:20:18APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE PROVIDE A NOTE TO INDICATE REQUIRED SEPARATE
 PERMITS FOR THE LOW VOLTAGE SYSTEMS. FBC 107.3
 2. CLARIFY BUS AMP RATING OF THE 42 SPACE PANEL BOARDS
 SHOWN AT 100AMP BUT NOT MANUFACTURED IN MORE THAN A
 30/40 SPACE DESIGN.
 3. THE ABOVE COMMENT IMPACTS THE BREAKER SIZE,
 EQUIPMENT GROUNDING CONDUCTOR SHOWN AS EXISTING ETC.
 PLEASE CLARIFY AND CORRELATE.
 4. PROVIDE SPECS SHEET FOR ALL EQUIPMENT TO INCLUDE THE
 NITROGEN GENERATOR, FORE PUMPS ETC. FBC 107.3.5
 5. PROVIDE A NOTE AT THE SERVICE TO LABEL AND ID PER
 NEC 230.2E. A NOTE WILL SUFFICE
 6. FEEL FREE TO CONTACT ME DIRECTLY SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
  
  