| Plan Review Notes For Permit 16040307 |
| Permit Number |
16040307 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-11 09:20:18 | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PLEASE PROVIDE A NOTE TO INDICATE REQUIRED SEPARATE | | | PERMITS FOR THE LOW VOLTAGE SYSTEMS. FBC 107.3 | | | 2. CLARIFY BUS AMP RATING OF THE 42 SPACE PANEL BOARDS | | | SHOWN AT 100AMP BUT NOT MANUFACTURED IN MORE THAN A | | | 30/40 SPACE DESIGN. | | | 3. THE ABOVE COMMENT IMPACTS THE BREAKER SIZE, | | | EQUIPMENT GROUNDING CONDUCTOR SHOWN AS EXISTING ETC. | | | PLEASE CLARIFY AND CORRELATE. | | | 4. PROVIDE SPECS SHEET FOR ALL EQUIPMENT TO INCLUDE THE | | | NITROGEN GENERATOR, FORE PUMPS ETC. FBC 107.3.5 | | | 5. PROVIDE A NOTE AT THE SERVICE TO LABEL AND ID PER | | | NEC 230.2E. A NOTE WILL SUFFICE | | | 6. FEEL FREE TO CONTACT ME DIRECTLY SHOULD YOU HAVE ANY | | | QUESTIONS OR CONCERNS. | | | | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|