| 2016-04-07 10:24:16 | JOB PERMIT NUMBER: 16040300 |
| | JOB ADDRESS: 201 SANTA LUCIA DR |
| | WEST PALM BEACH FLORIDA |
| | DATE: APRIL 7, 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | - THE SCOPE OF WORK ACCORDING TO FLORIDA STATUE |
| | 61G4-15.021 LIMITS THE CVC CONTRACTOR TO THE PV SUPPLY |
| | SIDE , THEREFORE ANY CONNECTION TO THE ELECTRICAL |
| | BUILDING PREMISES MUST BE DONE BY A LICENSED ELECTRICAL |
| | CONTRACTOR. |
| | - PLANS ARE MISSING LABELS AND MARKINGS |
| | 1 NEC 690.5 C GROUND FAULT PROTECTION |
| | 2 NEC 690.14 C 2 PERMANENTLY MARK DISCONNECT |
| | 3 NEC 690.31 E 3 IDENTIFY PV SOURCE CONDUCTORS |
| | 4 NEC 705.12 7 DO NOT RELOCATE SOURCE DISCONNECT |
| | - SITE CURRENT CODE STANDARDS NEC 2011 AND FBC 2014 |
| | |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |