| 2016-04-08 11:06:59 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THERE ARE NOT ANY REFERENCES OR DRAWINGS ON THE |
| | APPROVED PLANS THAT SHOW THE PHOTOVOLTAIC OR SOLAR |
| | WATER HEATER COLLECTOR ON THE ROOF OF THE MANUFACTURED |
| | BUILDING. THIS A SEPARATE PERMIT WITH AN APPLICATION |
| | DATE THAT PLACES IT UNDER THE 2014 FLORIDA BUILDING |
| | CODE RESIDENTIAL. THE APPLICABLE CODES ARE THE 2014 |
| | FBC-R AND THE 2011 NEC. PLEASE REVISE THE PLANS |
| | ACCORDINGLY. |
| | |
| | 2) THERE IS A SOLAR WATER HEATER COLLECTOR SHOWN ON |
| | SHEET S-1 OF THE DRAWINGS, HOWEVER, NO OTHER |
| | INFORMATION WAS PROVIDED. IF THIS IS TO BE INSTALLED, A |
| | SEPARATE PERMIT, APPLICATION AND REVIEWS ARE REQUIRED. |
| | |
| | 3) PROVIDE DOCUMENTATION FROM THE MANUFACTURED BUILDING |
| | DESIGNER OF RECORD TO SHOW THAT THE BUILDING CAN SAFELY |
| | SUPPORT ALL ADDITIONAL LOADING THAT MAY BE CREATED BY |
| | INSTALLATION OF THIS PHOTOVOLTAIC SYSTEM AND SOLAR |
| | WATER HEATER COLLECTOR ON THE ROOF. FBC-R 301.1 |
| | |
| | 4) THE STRUCTURAL MOUNTING DETAILS THAT WERE SUBMITTED |
| | ON SHEET S-2 ARE FOR A DIFFERENT TYPE OF ROOF |
| | CONSTRUCTION THAN THE ONE THAT WAS PERMITTED. THE |
| | APPROVED PLANS SHOW A 60 MIL TPO MEMBRANE ROOF COVERING |
| | OVER 1/4" TAPERED ISO OVER ZIP BOARD ROOF SHEATHING |
| | ATTACHED TO 22 GA. STEEL 1-1/2" CORRUGATED B DECK ON 8" |
| | X 2" 16 GA. STEEL JOISTS SPACED 24" O.C. THE |
| | CALCULATIONS AND DETAILS THAT WERE SUBMITTED ARE FOR |
| | ATTACHMENT TO WOOD TRUSSES USING LAG SCREWS. PLEASE |
| | CORRECT. FBC 107.2.1 |