| 2016-04-11 17:58:42 | JOB PERMIT NUMBER: 16040257 |
| | JOB ADDRESS: 1617 N FLAGLER DR |
| | WEST PALM BEACH FLORIDA |
| | DATE: APRIL 11 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | - SITE CURRENT CODE STANDARDS NEC 2011 AND FBC 2014, |
| | NEC 2008 NO LONGER APPLICABLE. |
| | - FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE |
| | SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE |
| | LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON |
| | FLOOR PLAN. THE PLANS ARE MISSING COFFEE MAKER , SHOWS |
| | 2 DISHWASHER ON FLOOR PLANS AND CLACS REFLECT ONLY 1 , |
| | REFLECT THESE LOADS ON PANEL A. |
| | - ADD THE FOLLOWING GENERAL ELECTRICAL NOTES : NEC |
| | 406.11 TAMPER RESISTANT RECEPTACLES , NEC 210.12 B AFCI |
| | PROTECTION , FBC-E C 404.1.1 / 402.4.4 RECESSED LIGHTS |
| | SHALL BE 75 % HIGH EFFICIENT AS WELL AS IC RATED AND |
| | SEALED TO NOT COMPROMISE BUILDING THERMAL ENVELOPE. ( 2 |
| | CFM ) |
| | - NEC 404.2 C PROVIDE A GROUNDED CONDUCTOR AT EACH |
| | SWITCH LOCATION. |
| | - NEC 210.52 , 210.8 BALCONY RECEPTACLES MUST BE GFCI |
| | PROTECTED. |
| | - NFPA SECTION 29.8.3.4(6). SMOKE ALARMS AND SMOKE |
| | DETECTORS SHALL NOT BE INSTALLED WITHIN A 36 IN. (910 |
| | MM) HORIZONTAL PATH FROM A DOOR TO A BATHROOM |
| | CONTAINING A SHOWER OR TUB UNLESS LISTED FOR |
| | INSTALLATION IN CLOSE PROXIMITY TO SUCH LOCATIONS. |
| | RELOCATE THE UNITS ACCORDINGLY. ( BY GUEST BEDROOM 1 & |
| | 2. ) |
| | - ALL ELECTRICAL BOXES IN A DEMISING WALL SHALL COMPLY |
| | WITH NEC 300.21 & FBC-B SECTION 714. ANY FIRE RATED |
| | STRUCTURE OR SURFACE THAT IS COMPROMISED SHALL BE |
| | RETURNED TO ITS ORIGINAL FIRE-RATING WITH APPROVED FIRE |
| | SEALING MATERIAL. |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |