| Plan Review Notes For Permit 16040212 |
| Permit Number |
16040212 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-06-21 14:37:37 | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: 2ND REQUEST COMMENTS FROM FIRST | | | REVIEW WERE NOT ADDRESSED | | | | | | | | | 1. IT IS UNCLEAR HOW THE VENTS FOR THE TOILETS AND | | | SHOWERS ARE CONNECTING TO THE SANITARY , YOU DO NOT | | | NEED SEPARATE VENTS FOR THESE FIXTURES THE VENT ON THE | | | LAVATORY SERVES AS THE VENT FOR THE WHOLE BATHROOM | | | GROUP PLEASE CLARIFY. PER WPB AMEND. TO FBC 107.2.1 | | | | | | 2. BOTH SETS OF PLANS INDICATE A 75 GAL WATER HEATER | | | ONE NEW ONE IS EXISTING IT SEEMS A LITTLE LARGE FOR A | | | ON BATHROOM UNIT ARE YOU SURE THIS IS CORRECT PLEASE | | | CLARIFY. PER WPB AMEND. TO FBC SEC. 107.2.1 |
|