| Date |
Text |
| 2016-06-06 15:52:59 | BUILDING PLAN REVIEW |
| | 2014 FLORIDA BUILDING CODE |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER ? PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-7918 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 2ND REVIEW |
| | DATE: 6/6/16 |
| | ACTION: FAIL |
| | |
| | MAIN HOUSE SCOPE OF WORK CHANGED TO WINDIWS, DOORS AND |
| | SIDING. |
| | |
| | 1. COMPLY WITH HISTORIC REVIEW COMMENTS. |
| | 2. PRODUCT APPROVALS SUBMITTED ARE FOR SINGLE HUNG |
| | WINDOWS. WINDOW SCHEDULE ON PG. A1 DOES NOT LIST ANY |
| | SINGLE HUNG WINDOWS. PROVIDE PRODUCT APPROVALS FOR |
| | WINDOWS, DOORS AND SIDING. DESIGNER TO REVIEW AND SIGN |
| | PRODUCT APPROVALS. ALL PRODUCT APPROVALS ON WINDOW AND |
| | DOOR SCHEDULE ARE EXPIRED. |
| | 3. PG T1 INDICATES GOVERNING CODES AS 2008 FBC. CURRENT |
| | GOVERNING CODES ARE 2014 FBC 5TH ED. |
| | 4. FLOOR PLAN DETAIL ON PLAN SHEET S-1 IS A COPY OF |
| | EXPIRED NOA 02-1120-03. |
| | |
| | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY |
| | FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE WINDOW AND |
| | DOOR SUBMITTALS. |
| | |
| | |
| | |
| | |
| 2016-05-18 14:42:44 | BUILDING PLAN REVIEW |
| | W.P.B. PERMIT NO.: 16040210 |
| | ADD: 504 50TH ST |
| | CONTR: OWNER - STELIOS HIOTIS |
| | TEL: 561-419-1258 |
| | E-MAIL: ? |
| | |
| | 2014 FLORIDA BUILDING CODE |
| | W/ 2014 WEST PALM BEACH AMENDMENTS |
| | TO THE FLORIDA BUILDING CODE, CHPT. 1, ADMINISTRATION |
| | |
| | 2ND REVIEW |
| | DATE: 5/18/16 |
| | ACTION: FAILED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | |
| | 1. ORIGINAL SOW CHANGED ON 4/19/16 PER SAK. NEW SOW FOR |
| | WINDOWS, DOORS AND SIDING ON MAIN HOUSE, ONLY. |
| | |
| | 2. INCORRECT CODE REFERENCED ON PLANS. CURRENT CODE IS |
| | THE 2014 FBC 5TH ED. |
| | |
| | 3. SELECTED WINDOWS DO NOT COMPLY WITH THE HISTORIC |
| | REQUIREMENTS FOR THIS PROPERTY. COMPLY WITH HISTORIC |
| | COMMENTS AND RE-APPLY. |
| | |
| | 4. PROVIDE PRODUCT APPROVALS FOR THOSE ITEMS SUBJECT TO |
| | WIND LOAD. (WINDOWS, DOORS, SIDING). |
| | |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. (SEE ALSO SECTION 107.3.5). |
| | |
| | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY |
| | FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE WINDOW, DOOR |
| | AND SIDING SUBMITTALS. |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER ? PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-7918 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |