| 2016-06-21 14:33:33 | REVIEW: FBC 2014 |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: COMMENTS FROM FIRST REVIEW NOT |
| | ADDRESSED 2ND REQUEST |
| | |
| | 1. SHT. A-1 PROPOSED LAUNDRY IT APPEARS THAT YOU HAVE |
| | WASHING MACHINE MARKED AS D.W FOR DISHWASHER PLEASE |
| | CLARIFY. PER WPB AMEND. TO FBC 107.2.1 |
| | |
| | 2. SHT A-1 RISER DIAGRAM THE WASHING MACHINE SHALL NOT |
| | CONNECT DIRECTLY TO SANITARY IT MUST DRAIN INTO A STAND |
| | PIPE WITH AN AIR BREAK. PER FBC PL SEC. P2718.1 |
| | |
| | 3. SHT A-1 RISER DIAGRAM THE DISHWASHER DRAIN SHALL NOT |
| | CONNECT DIRECTLY TO SANITARY IT HAS TO CONNECT TO SINK |
| | DRAIN OR DISPOSAL WITH AN AIR BREAK. PER FBC PL SEC. |
| | P2717.1 |
| | |
| | 4. IT IS UNCLEAR HOW THE VENTS FOR THE TOILETS AND |
| | SHOWERS ARE CONNECTING TO THE SANITARY , YOU DO NOT |
| | NEED SEPARATE VENTS FOR THESE FIXTURES THE VENT ON THE |
| | LAVATORY SERVES AS THE VENT FOR THE WHOLE BATHROOM |
| | GROUP PLEASE CLARIFY. PER WPB AMEND. TO FBC 107.2.1 |
| | |
| | 5. THE LAUNDRY SHALL TIE IN DOWNSTREAM OF THE BATHROOM |
| | GROUP. PER FBC PL SEC. P3108.1 |
| 2016-05-31 17:50:20 | 1ST REVIEW: FBC 2014 |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. A-1 PROPOSED LAUNDRY IT APPEARS THAT YOU HAVE |
| | WASHING MACHINE MARKED AS D.W FOR DISHWASHER PLEASE |
| | CLARIFY. PER WPB AMEND. TO FBC 107.2.1 |
| | |
| | 2. SHT A-1 RISER DIAGRAM THE WASHING MACHINE SHALL NOT |
| | CONNECT DIRECTLY TO SANITARY IT MUST DRAIN INTO A STAND |
| | PIPE WITH AN AIR BREAK. PER FBC PL SEC. P2718.1 |
| | |
| | 3. SHT A-1 RISER DIAGRAM THE DISHWASHER DRAIN SHALL NOT |
| | CONNECT DIRECTLY TO SANITARY IT HAS TO CONNECT TO SINK |
| | DRAIN OR DISPOSAL WITH AN AIR BREAK. PER FBC PL SEC. |
| | P2717.1 |
| | |
| | 4. IT IS UNCLEAR HOW THE VENTS FOR THE TOILETS AND |
| | SHOWERS ARE CONNECTING TO THE SANITARY , YOU DO NOT |
| | NEED SEPARATE VENTS FOR THESE FIXTURES THE VENT ON THE |
| | LAVATORY SERVES AS THE VENT FOR THE WHOLE BATHROOM |
| | GROUP PLEASE CLARIFY. PER WPB AMEND. TO FBC 107.2.1 |
| | |
| | 5. THE LAUNDRY SHALL TIE IN DOWNSTREAM OF THE BATHROOM |
| | GROUP. PER FBC PL SEC. P3108.1 |