| 2016-06-22 07:48:02 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16040208 |
| | ADD: 435 6TH ST. |
| | CONT: BATTEN CONSTRUCTION |
| | TEL: 561-820-0027 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: WED. JUNE 22/2016 |
| | ACTION: DENIED |
| | |
| | |
| | 8) THE SUBMITTED CALCULATIONS BY P.E. PAUL WALSH ARE |
| | COPIES NOT ORIGINALS. 61G15-23.002(2) FL. ADMIN. CODE. |
| | A COVER SHEET OR INDEX SHEET FOR ENGINEERING |
| | SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE |
| | SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION & |
| | PREPARATION OF EACH SECTION OF THE ENGINEERING |
| | SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER |
| | SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER |
| | THE COVER SHEET OR INDEX SHEET. . |
| | |
| | COMMENT FROM THE 2ND REVIEW. THE PLANS ARE DEFICIENT IN |
| | HOW THE RTU WILL BE FASTENED TO THE ROOF TOP CURB NOR |
| | THE ROOF TOP CURB TO THE MWFRS (MAIN WIND FORCE |
| | RESISTING SYSTEM. FOR ALL ROOF TOP EQUIPMENT, CURBS OR |
| | A/C STANDS, DETAILED ATTACHMENT TO THE ROOF FRAMING & |
| | DECK AS WELL AS FROM THE CURB OR ROOF STAND TO THE |
| | EQUIPMENT ABOVE. 2014 FBC-B 1604.4 ANALYSIS. LOAD |
| | EFFECTS ON STRUCTURAL MEMBERS AND THEIR CONNECTIONS |
| | SHALL BE DETERMINED BY METHODS OF STRUCTURAL ANALYSIS |
| | THAT TAKE INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY, |
| | GEOMETRIC COMPATIBILITY AND BOTH SHORT- AND LONG-TERM |
| | MATERIAL PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED |
| | TO RESIST THE OVERTURNING EFFECTS CAUSED BY THE LATERAL |
| | FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR |
| | WIND LOADS? |
| | |