2016-06-09 09:37:12FLORIDA ENERGY CODE FBC 2014
  
  
 R403.6.1 - HEATING AND COOLING EQUIPMENT SHALL BE SIZED
 IN ACCORDANCE WITH ACCA MANUAL S
 BASED ON THE EQUIPMENT LOADS CALCULATED IN ACCORDANCE
 WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING
 LOADS FOR THE DIRECTIONAL ORIENTATION OF THE BUILDING.
 THE MANUFACTURER AND MODEL
 NUMBER OF THE OUTDOOR AND INDOOR UNITS (IF SPLIT
 SYSTEM) SHALL BE SUBMITTED ALONG
 WITH THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE
 DESIGN CONDITIONS DESCRIBED IN
 SECTION R302.1. THIS CODE DOES NOT ALLOW DESIGNER
 SAFETY FACTORS, PROVISIONS FOR
 FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT
 EQUIPMENT SIZING. SYSTEM SIZING
 CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY LOCAL
 INTERMITTENT MECHANICAL
 VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM
 EXHAUST SYSTEMS.
  
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER