| Plan Review Notes For Permit 16040208 |
| Permit Number |
16040208 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-07 13:23:54 | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED REPLACED SHEETS DETACHED. | | | | | | FLORIDA BUILDING CODE 5TH EDITION (2014) | | | ENERGY CONSERVATION | | | | | | SECTION R202 RENOVATED BUILDINGS - A RESIDENTIAL OR | | | NONRESIDENTIAL BUILDING UNDERGOING ALTERATION THAT | | | VARIES INSULATION, HVAC SYSTEMS, WATER HEATING SYSTEMS, | | | OR EXTERIOR ENVELOPE CONDITIONS, PROVIDED THE ESTIMATED | | | COST OF RENOVATION EXCEEDS 30 PERCENT OF THE ASSESSED | | | VALUE OF THE STRUCTURE. | | | | | | R403.6.1 - PROVIDE HEAT LOAD CALCULATIONS. | | | | | | 107.2.1 - PROVIDE DRAWING OF ALL DUCT WORK (TO INCLUDE | | | DUCT SIZES, SUPPLY/RETURN CFM QUANTITIES AND GRILL | | | SIZES) |
|