Plan Review Notes
Plan Review Notes For Permit 16040208
Permit Number 16040208
Review Stop M
Sequence Number 1
Notes
Date Text
2016-04-07 13:23:54WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED REPLACED SHEETS DETACHED.
  
 FLORIDA BUILDING CODE 5TH EDITION (2014)
 ENERGY CONSERVATION
  
 SECTION R202 RENOVATED BUILDINGS - A RESIDENTIAL OR
 NONRESIDENTIAL BUILDING UNDERGOING ALTERATION THAT
 VARIES INSULATION, HVAC SYSTEMS, WATER HEATING SYSTEMS,
 OR EXTERIOR ENVELOPE CONDITIONS, PROVIDED THE ESTIMATED
 COST OF RENOVATION EXCEEDS 30 PERCENT OF THE ASSESSED
 VALUE OF THE STRUCTURE.
  
 R403.6.1 - PROVIDE HEAT LOAD CALCULATIONS.
  
 107.2.1 - PROVIDE DRAWING OF ALL DUCT WORK (TO INCLUDE
 DUCT SIZES, SUPPLY/RETURN CFM QUANTITIES AND GRILL
 SIZES)