| Plan Review Notes For Permit 16040208 |
| Permit Number |
16040208 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-06 16:11:01 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PLEASE SHOW A RECEPTACLE OUTLET WP/WR GFCI PROTECTED | | | AT THE ROOFTOP WITHIN 25FT OF MECHANICAL UNIT PER NEC | | | 210.63 AND REFLECT ON REVISED PANEL SCHEDULE. | | | 2. PROVISO WILL BE GRANTED IF OTHER PENDING TRADE | | | REVIEWERS APPROVE PLANS. | | | 3. FEEL FREE TO CONTACT ME WITH ANY QUESTIONS OR | | | CONCERNS. | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|