Plan Review Notes
Plan Review Notes For Permit 16040208
Permit Number 16040208
Review Stop E
Sequence Number 1
Notes
Date Text
2016-04-06 16:11:01INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE SHOW A RECEPTACLE OUTLET WP/WR GFCI PROTECTED
 AT THE ROOFTOP WITHIN 25FT OF MECHANICAL UNIT PER NEC
 210.63 AND REFLECT ON REVISED PANEL SCHEDULE.
 2. PROVISO WILL BE GRANTED IF OTHER PENDING TRADE
 REVIEWERS APPROVE PLANS.
 3. FEEL FREE TO CONTACT ME WITH ANY QUESTIONS OR
 CONCERNS.