| 2016-05-18 14:03:58 | JOB PERMIT NUMBER: 16040196 |
| | JOB ADDRESS: 531 SOUTHERN BLVD. |
| | WEST PALM BEACH FLORIDA |
| | DATE: MAY 18 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | THESE ARE COMMENTS TO YOUR RESPONSES! |
| | |
| | - 1) NEW SET OF PLANS DON?T SHOW NEC 2011 IN THE |
| | GENERAL DEMO NOTES AS PREVIOUSLY REQUESTED. |
| | - 2) THE MANUFACTURE CUT SHEETS FOR THE GENERATOR AND |
| | ATS EQUIPMENT WEREN?T PROVIDED WITH THE SUBMITTAL. |
| | GENERATOR PERMITS ARE ISSUED SEPARATELY. |
| | - 3) THE SITE PLAN WAS RECOGNIZED AND DOES SHOW THE |
| | LOCATION OF THE GENERATOR. COMPLIED. |
| | - 4) THE SERVICE RISER DIAGRAM DOESN?T INDICATE A |
| | GROUNDING DETAIL PER NEC 250.30(6) ALL SEPARATELY |
| | DERIVED SYSTEM GROUNDING SHALL BE TIED IN WITH A TAP TO |
| | A COMMON ELECTRODE CONDUCTOR AT THE SAME POINT AT EACH |
| | SYSTEM. |
| | - 5) PLEASE ADD NEC 110.15 HIGH LEG MARKING TO THE |
| | RISER DIAGRAM, NEC 110.16 ARC-FLASH HAZARD WARNING |
| | LABEL, & NEC 110.24 AVAILABLE FAULT CURRENT MARKINGS. |
| | FURTHERMORE A PERMANENT PLAQUE SHALL BE INSTALLED TO |
| | IDENTIFY ALL SERVICES, FEEDERS, AND BRANCH CIRCUITS |
| | POWERING THE BUILDING. NEC 230.2(E). |
| | - 6) IT WAS UNDERSTOOD THAT THE GENERATOR ISN?T A |
| | SEPARATELY DERIVED SYSTEM THEREFORE DOESN?T NEED TO BE |
| | LISTED AS SERVICE RATED. COMPLIED. |
| | - 7) IT WAS UNDERSTOOD THAT THE GENERATOR ISN?T A |
| | SEPARATELY DERIVED SYSTEM THEREFORE DOESN?T NEED TO BE |
| | LISTED AS SERVICE RATED. JUST FOR CLARIFICATION IN THE |
| | FUTURE JUST SHOW GROUND ROD AS AN AUXILIARY GROUNDING |
| | ELECTRODE. COMPLIED. |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |