| 2016-04-21 10:14:04 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16040196 |
| | ADD: 531 SOUTHERN BLVD SUITE # ???? |
| | CONT: ALONSO & ASSOCIATES |
| | TEL: 561-837-9820 |
| | E-MAIL: AALONSO@ALONSOAND ASSOCIATES.COM |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. APRIL 21/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-202: |
| | |
| | 1A) THE RESTROOM WILL NEED TO SHOW THE SIZE OF THE |
| | LAVATORY TO SHOW COMPLIANCE WITH THE: |
| | |
| | 2014 FBC-ACCESSIBILITY CODE 604.3.1 SIZE. |
| | CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| | (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| | WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED |
| | PERPENDICULAR FROM THE REAR WALL. |
| | |
| | 1B) THE RESTROOM ALSO SHOWS A SHOWER WITH A DEPTH OF 2 |
| | FEET 8 INCHES, PLEASE PROVIDE COMPLIANCE WITH SECTION |
| | 608.2.2 FBC-ACCESS. CODE MINIMUM DEPTH OF 36 INCHES. |
| | |
| | 1C) THE ACCESSIBLE RESTROOM SHOWER SHOWS A SEAT IN THE |
| | SHOWER BUT THE WALL EXTENDS PAST THE END OF THE SEAT. |
| | PLEASE REVIEW 2014 FBC-ACCESSIBILITY CODE FIGURE |
| | 608.2.1 & FIGURE 608.2.2. |
| | |
| | 2) PLEASE SHOW AN ACCESSIBLE ENTRANCE INTO THE TENANT |
| | SPACE. 2014 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS |
| | OF EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). |
| | |
| | 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| | IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| | ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| | SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| | |
| | PLEASE NOTE IF THE NEW SWING DOOR IN THE NORTHEAST |
| | CORNER OF THE BUILDING IS GOING TO BE THE ACCESSIBLE |
| | ENTRANCE THEN THERE NEEDS TO BE A 5-0 FOOT TURNING |
| | RADIUS AT THE DOOR. ACCESS. CODE |
| | 405.7.4 CHANGE IN DIRECTION. RAMPS THAT CHANGE |
| | DIRECTION BETWEEN RUNS AT LANDINGS SHALL HAVE A CLEAR |
| | LANDING 60 INCHES (1525 MM) MINIMUM BY 60 INCHES (1525 |
| | MM) MINIMUM. |
| | |
| | 405.7.5 DOORWAYS. |
| | WHERE DOORWAYS ARE LOCATED ADJACENT TO A RAMP LANDING, |
| | MANEUVERING CLEARANCES REQUIRED BY 404.2.4 AND 404.3.2 |
| | SHALL BE PERMITTED TO OVERLAP THE REQUIRED LANDING |
| | AREA. SEE FIGURE 404.2.4.1(H) |
| | THE TOP OF THE RAMP HAS TO TRANSITION INTO A LEVEL |
| | LANDING AND HAVE 2-0 FEET BEFORE THE CLOSEST PORTION OF |
| | THE DOOR. |
| | |
| | |
| | 3) DISCREPANCY IN SHEETS A-202 & A-203. SHEET A-202 THE |
| | TENANT SEPARATION WALL IS SHORTER THAN DEPICTED IN |
| | A-203. DISCREPANCY, 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 4) SHEET A-201 IN THE NORTHEAST CORNER OF THE BUILDING |
| | INDICATES THE REMOVAL OF A OVERHEAD DOOR. SHEET A-202 |
| | SHOWS A NEW EXTERIOR SWING DOOR AND WALL INFILL. THE |
| | PLANS DO NOT PROVIDE ANY INFORMATION AS TO WHAT |
| | MATERIALS ARE TO BE USED IN THE INFILL, COLUMNS AND |
| | BLOCK, STEEL STUDS, ETC? |
| | 107.2.1.3 ADDITIONAL INFORMATION./ 107.3.5.1.1(8) |
| | BUILDING ENVELOPE, MINIMUM PLAN REVIEW CRITERIA FOR |
| | COMMERCIAL BUILDINGS. |
| | |
| | 5) THE PLANS WILL ALSO NEED TO PROVIDE COMPLIANCE WITH |
| | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | |
| | 6A) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: (31)(A) EXTERIOR DOORS. |
| | |
| | 6B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC... |
| | |
| | 7) SHEET A-202 THE RESTROOM GRAB RAILS ARE MEASURED TO |
| | THE CENTERLINE OF THE GRAB RAIL. PLEASE BE AWARE OF THE |
| | CHANGE IN THE 2014 ACCESS. CODE FOR THE HEIGHT OF GRAB |
| | BARS AND THE MEASURING OF GRAB BARS IS NOW FROM FINISH |
| | FLOOR TO THE TOP OF THE GRASPING SURFACE OF THE GRAB |
| | BAR. |
| | 2014 FBC-ACCESS. CODE A609.4 POSITION OF GRAB BARS. |
| | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| | 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) |
| | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| | THE GRIPPING SURFACE. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |