| Notes |
| Date |
Text |
| 2016-04-07 15:38:52 | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED REPLACED SHEETS DETACHED. | | | | | | 107.2.1 - CONFIRM CFM QUANTITY OF AHU RH1T2417STANJA. | | | AS PER RUDD/RHEEM RHIT/RH2T SERIES AHU MANUFACTURER | | | SPECIFICATIONS THE HIGH SPEED IS 800 CFM AND LOW SPEED | | | IS 600 CFM. AHU #2 AS PER THE PLANS SUBMITTED SHOW 933 | | | CFM FOR THE SPECIFIC AREA IT SUPPLIES. | | | | | | PROVIDE FBC 2014 WINDLOAD REQUIREMENT TIE DOWN DETAILS | | | FOR CONDENSERS.(SEE NOTES ON SUBMITTED DETAIL). |
|