| 2016-04-06 16:33:16 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1. SHEET A 1 - THERE IS NO REFERENCE TO THE APPLICABLE |
| | FIRE CODE INDICATED. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | |
| | 2. SHEET A 2 - THE EXTENT OF THE REMODEL OR REVISION IS |
| | UNCLEAR AND DOES NOT INDICATE SUFFICIENT DETAIL TO |
| | ADDRESS LIFE SAFETY SYSTME CONCERNS OF THE PROPOSED |
| | PROJECT. |
| | |
| | THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF ANY |
| | FIRE ALARM AND FIRE SPRINKLER SYSTEM EQUIPMENT FOR CODE |
| | COVERAGE AND COMPLIANCE. ANY REMOVAL AND/OR |
| | CONSTRUCTION OF WALLS REQUIRE AN EVALUATION OF THE |
| | EXISTING EQUIPMENT. |
| | |
| | IF EXISTING, THE FIRE ALARM AND FIRE SPRINKLER SYSTEM |
| | SHALL REMAIN ACTIVE THROUGHOUT THE CONSTRUCTION PERIOD. |
| | |
| | ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE |
| | UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE |
| | SAFETY CONTRACTORS. |
| | |
| | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEM, EXCEEDS 4 |
| | HOURS, A FIRE WATCH SHALL BE IMPLEMENTED AND MAINTAINED |
| | UNTIL FULL AND COMPLETE PROTECTION IS RETURNED. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |