| 2016-04-13 14:11:34 | 1ST REVIEW 4/13/16 |
| | 2014 5TH FBC ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 516-805-6713 |
| | |
| | |
| | |
| | -107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| | ELECTRONIC MEDIA DOCUMENTS SHALL BE |
| | SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. (SEE ALSO SECTION 107.3.5). |
| | |
| | |
| | - PLANS ARE SKETCHED WITH PENCIL WHICH IS NON PERMANET |
| | , THERES A HOME DEPOT SEAL STATING NOT TO COPYWRITE |
| | THERE PLANS. |
| | - ADD GENERAL ELECTRICAL NOTES NEC 406.11 TAMPER |
| | RESISTANT RECEPTACLES , FBC-ER 404.1.1 / 402.4.4 |
| | RECESSED LIGHTS SHALL BE 75 % HIGH EFFICIENT AS WELL AS |
| | IC RATED AND SEALED TO NOT COMPROMISE BUILDING THERMAL |
| | ENVELOPE. ( 2CFM ), SMOKE ALARMS PER RESIDENTIAL CODE |
| | SECTIONS 314 & 315. |