Plan Review Notes For Permit 16040171
Permit Number 16040171
Review Stop E
Sequence Number 1
Notes
Date Text
2016-04-13 14:11:341ST REVIEW 4/13/16
 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
  
  
  
 -107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
  
 - PLANS ARE SKETCHED WITH PENCIL WHICH IS NON PERMANET
 , THERES A HOME DEPOT SEAL STATING NOT TO COPYWRITE
 THERE PLANS.
 - ADD GENERAL ELECTRICAL NOTES NEC 406.11 TAMPER
 RESISTANT RECEPTACLES , FBC-ER 404.1.1 / 402.4.4
 RECESSED LIGHTS SHALL BE 75 % HIGH EFFICIENT AS WELL AS
 IC RATED AND SEALED TO NOT COMPROMISE BUILDING THERMAL
 ENVELOPE. ( 2CFM ), SMOKE ALARMS PER RESIDENTIAL CODE
 SECTIONS 314 & 315.