| 2016-04-05 08:38:43 | 1ST REVIEW: FBC 2014 5TH ED | | | CHRISTOPHER S. THROOP, C.B.O. | | | BLDG. PLANS EXAMINER ? PX3169 | | | (561) 805-6718 | | | [email protected] | | | | | | 1. PROVIDE PROPOSED UNDERLAYMENT. | | | 2. PROVIDE AIR-BOURNE AND IMPACT SOUND TEST'S FOR | | | UNDERLAYMENT. | | | 3. PROVIDE FLAME SPREAD TEST FOR UNDERLAYMENT. | | | | | | FBC 603.1 FLAME SPREAD | | | | | | FBC 1207.2 AIR-BORNE SOUND. ASTM E 09-02 | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-04 | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | |
|