Plan Review Notes
Plan Review Notes For Permit 16040056
Permit Number 16040056
Review Stop M
Sequence Number 3
Notes
Date Text
2016-06-30 10:55:173RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040056
 6/30/16
  
 1) THE REVISED FAN SCHEDULE INDICATES EF-2 IS FOR
 WORKROOM #2, BUT THE THE PLAN SHOWS IT IN OFFICE #3.
 PLEASE NOTE THAT THE ELECTRICAL PLAN DOES NOT SHOW A
 SWITCH FOR THIS FAN.
  
 2) REQUIRED RETURN AIR FROM OFFICE #3 IS NOT SHOWN ON
 THE PLAN.
  
 3) REFER TO TABLE 403.3 FOOTNOTE B AND CLARIFY HOW THE
 REQUIREMENT FOR NON-RECICULATION OF AIR TO THE BEAUTY
 SALON IS BEING ACHIEVED. ARE THE EXHAUST FANS TO BE
 LINKED TO THE AC SYSTEMS?
  
 4) THE MISSING PAGE #6 OF THE ENERGY CALCULATION FORM
 HAS BEEN SUBMITTED BUT NOT INSERTED INTO THE DOCUMENT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  