| Plan Review Notes For Permit 16040056 |
| Permit Number |
16040056 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-06-30 10:55:17 | 3RD REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16040056 | | | 6/30/16 | | | | | | 1) THE REVISED FAN SCHEDULE INDICATES EF-2 IS FOR | | | WORKROOM #2, BUT THE THE PLAN SHOWS IT IN OFFICE #3. | | | PLEASE NOTE THAT THE ELECTRICAL PLAN DOES NOT SHOW A | | | SWITCH FOR THIS FAN. | | | | | | 2) REQUIRED RETURN AIR FROM OFFICE #3 IS NOT SHOWN ON | | | THE PLAN. | | | | | | 3) REFER TO TABLE 403.3 FOOTNOTE B AND CLARIFY HOW THE | | | REQUIREMENT FOR NON-RECICULATION OF AIR TO THE BEAUTY | | | SALON IS BEING ACHIEVED. ARE THE EXHAUST FANS TO BE | | | LINKED TO THE AC SYSTEMS? | | | | | | 4) THE MISSING PAGE #6 OF THE ENERGY CALCULATION FORM | | | HAS BEEN SUBMITTED BUT NOT INSERTED INTO THE DOCUMENT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|