| Plan Review Notes For Permit 16040056 |
| Permit Number |
16040056 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-06-10 09:57:07 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16040056 | | | 6/10/16 | | | | | | 1) AS PREVIOUSLY NOTED IN THE 1ST REVIEW, THE | | | COMPLIANCE SUMMARY DATA FOR THE NEW AC SYSTEM (PAGE 6) | | | IS MISSING FROM THE ENERGY GAUGE SUBMITTAL. | | | | | | 2) SHEET A/C-1: THE EXHAUST DUCT FROM THE TOILET ROOM | | | CANNOT BE CONNECTED WITH THE DUCT FROM THE SALON- | | | SECTION 501.2. | | | | | | 3) A/C-1: PER THE NOTE UNDER THE AIR BALANCE SCHEDULE, | | | THE TOILET EXHAUST MUST HAVE A CAPACITY OF 70 CFMS- | | | TABLE 403.3 FOOTNOTE E. | | | | | | 4) A-1 & A/C-1: THE FLOOR PLANS FOR THE LOFT ON THESE | | | TWO PLAN SHEETS DO NOT MATCH- OFFICE #1 IS NOT SHOWN ON | | | THE AC PLAN. PLEASE CLARIFY THE USE OF THE SINKS IN THE | | | LOFT OFFICES. ARE THESE ROOMS ACTUALLY SALON ROOMS? WHY | | | IS THERE AN EXHAUST FAN IN OFFICE #3? PLEASE NOTE | | | EXHAUST FOR OFFICE #1 MAY ALSO BE REQUIRED AND BOTH | | | SYSTEMS ADDED TO THE AIR BALANCE CALCULATIONS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|