| 2016-06-03 10:38:39 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16040056 |
| | ADD: 610 CLEMATIS ST. # 106 |
| | CONT: PRETI CONSTRUCTION |
| | TEL: 561-840-9949 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JUNE 03/ 2016 / JUNE 16/2016 RE-REVIEWED |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-1: |
| | 1A-B) COMPLIED |
| | |
| | 1C) SEMI-COMPLIED. THE PLANS DO NOT MENTION THE |
| | REQUIREMENT FOR 1 HOUR FIRE RESISTANCE RATED WALLS PER |
| | SEE 2014 1009.9.4 ENCLOSURES UNDER EXTERIOR STAIRWAYS. |
| | 1ST ROUND COMMENTS. THE EXISTING STAIR TO THE LOFT AREA |
| | SHOWS A NEW CLOSET AND WOOD FULL LOUVER DOOR. PLEASE |
| | SEE 2014 1009.9.4 ENCLOSURES UNDER EXTERIOR STAIRWAYS. |
| | THERE SHALL BE NO ENCLOSED USABLE SPACE UNDER EXTERIOR |
| | EXIT STAIRWAYS UNLESS THE SPACE IS COMPLETELY ENCLOSED |
| | IN 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION. THE OPEN |
| | SPACE UNDER EXTERIOR STAIRWAYS SHALL NOT BE USED FOR |
| | ANY PURPOSE. |
| | |
| | 1D) COMPLIED. |
| | |
| | 1E) COMPLIED. 6/16/16. NOTE 15. SHEET A-1 HAS NOT GIVEN |
| | ANY DETAILS FOR THE HEIGHT OF THE WORK AREA COUNTERS. |
| | PLEASE PROVIDE COMPLIANCE WITH: 2014 FBC-ACCESS. CODE |
| | 902.3 HEIGHT. THE TOPS OF WORK SURFACES SHALL BE 28 |
| | INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 1F) 2ND REQUEST. THE PLANS NOW INDICATE THE ACCESSIBLE |
| | ENTRANCE IS VIA CORRIDOR TO THE TENANT SPACE. PLEASE |
| | PROVIDE A FLOOR PLAN SHOWING THE ACCESSIBLE PATH OF |
| | TRAVEL TO THE TENANT SPACE. 2014 FBC-ACCESSIBILITY CODE |
| | 206.2.4 SPACES AND ELEMENTS. AT LEAST ONE ACCESSIBLE |
| | ROUTE SHALL CONNECT ACCESSIBLE BUILDING OR FACILITY |
| | ENTRANCES WITH ALL ACCESSIBLE SPACES AND ELEMENTS |
| | WITHIN THE BUILDING OR FACILITY WHICH ARE OTHERWISE |
| | CONNECTED BY A CIRCULATION PATH |
| | 1ST ROUND OF COMMENTS. PLEASE PROVIDE A DETAIL OF THE |
| | EXTERIOR OF THE BUILDING, SHOWING HOW COMPLIANCE WITH |
| | VERTICAL ACCESSIBILITY FROM THE CITY SIDEWALK TO THE |
| | FRONT ENTRY IS GOING TO BE ACHIEVED , THERE APPEARS TO |
| | BE 3 STEPS BEFORE ONE GAINS ENTRY TO THE INTERIOR OF |
| | THE TENANT SPACE. 2014 FBC-ACCESSIBILITY CODE 201.1.1. |
| | VERTICAL ACCESSIBILITY. PLEASE NOTE THIS UNIT WAS |
| | ORIGINALLY DESIGNED UNDER THE FAIR HOUSING CODE AND THE |
| | INTERIOR DOOR FROM THE CORRIDOR WAS ABLE TO BE |
| | CONSIDERED THE PRIMARY DOOR SINCE THE OCCUPANT WOULD BE |
| | GAINING ENTRY FROM THE GARAGE. BUILDING PERMITTED UNDER |
| | PERMIT 03031778. |
| | |
| | 1G) 2ND REQUEST. DOOR # 10 HAS BEEN RESIZED TO BEING A |
| | 2 FT. 8 IN. DOOR. PLEASE NOTE DOORS 8,9 & 10 ARE ALL |
| | POCKET DOORS AND NEED TO COMPLY WITH 2014 ACCESSIBILITY |
| | CODE 404.2.7 DOOR AND GATE HARDWARE. |
| | WHERE SLIDING DOORS ARE IN THE FULLY OPEN POSITION, |
| | OPERATING HARDWARE SHALL BE EXPOSED AND USABLE FROM |
| | BOTH SIDES. |
| | ACCESS. CODE 309.4 OPERATION. OPERABLE PARTS SHALL BE |
| | OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT |
| | GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE |
| | REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS |
| | (22.2 N) MAXIMUM. |
| | 1ST ROUND COMMENTS. PLEASE NOTE DOOR # 10 IS INDICATED |
| | TO BE A 2'-6" DOOR. 2014 FBC-ACCESS. CODE 404.2.3 CLEAR |
| | WIDTH. MINIMUM OF 32 INCHES CLEAR WIDTH. |
| | |
| | 1H-K) COMPLIED. |
| | |
| | 2) COMPLIED. COMPONENTS & CLADDING/ PRESSURES. |
| | |
| | 3) 2ND REQUEST. PLEASE BE AWARE THIS IS A CHANGE OF |
| | OCCUPANCY FOR THIS UNIT. THERE HAD BEEN A PERMIT ISSUED |
| | BUT NO WORK EVER TAKE PLACE, NO INSPECTIONS, THE PERMIT |
| | WAS VOIDED AT THE CONTRACTORS REQUEST. BEFORE A PERMIT |
| | TO CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID |
| | TO PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS |
| | MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID |
| | RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL |
| | (561)233-5025 FOR MORE INFORMATION. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |