| Plan Review Notes For Permit 16040056 |
| Permit Number |
16040056 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-03 09:25:40 | 1) THE WASHER /DRYER SHALL COMPLY WITH SEC.FL. ACCESS. | | | CODE SEC.214 & 611. INDICATE SO ON THE PLAN. SHOW THE | | | RREQUIRED CLEAR FLOOR SPACE AS REQUIRED BY FAC SEC.305. | | | OPERABLE PARTS SHALL CCOMPLY WITH FAC SEC.309 AND THE | | | HEIGHT OF TOP LOADING OR FRONT LOADING MACHINES SHALL | | | COMPLY WITH FAC SEC.611.4. | | | 2) THE SINK IN WORKROOM #1 & #2 SHALL COMPLY WITH THE | | | FAC SEC.212.1. | | | 3) THE SINK IN THE COLOR AREA SHALL COMPLY WITH 2014 | | | FAC SEC.212.3. | | | 4) THE SHOWER ON THE MEZZANINE LEVEL SHALL COMPLY WITH | | | FAC SEC.213, 213.2, 213.3.6 603, 608, 609, 610. PROVIDE | | | DETAILS. FBC 107.2.1. | | | 5) CLARIFY THE TYPE OF WORK TO BE DONE IN WORKROOMS #1 | | | & #2.FBC 107.2.1. | | | 6) THE "WASH AREA" IS CONSIDERED A BATHING ROOM AND | | | SHALL COMPLY WITH THE FAC SEC.213.2.UNISEX BATHING | | | ROOMS SHALL CONTAIN AT A MINIMUM ONE LAVATORY, ONE | | | SHOWER AND ONE WATER CLOSET. | | | 7) THA LAVATORY IN THE WASH AREA SHALL COMPLY WITH THE | | | 2014 FAC SEC.213.3.4 AND SEC. 606. | | | 8) THE GROUND FLOOR TOILET ROOM IS NOT SHOWN ON THE | | | WATER RISER DIAGRAM. FBC SEC. 107.3.5.1.3. | | | 9) THE SANITARY RISER ON SHEET P-1 SHOWS A FLAT, DRY | | | VENT FOR THE SHAMPOO SINKS WHICH IS NOT PERMITTED. THE | | | VENT SHALL CONNECT TO THE HORIZONTAL DRAIN ABOVE THE | | | CENTERLINE OF THE HORIZONTAL DRAIN PIPE. 2014 FPC SEC. | | | 905.3. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|