| 2016-08-22 10:48:34 | 2ND REVIEW: FBC 2014 |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: 2ND REQUEST |
| | |
| | |
| | |
| | |
| | 1. THE MIRROR SHALL COMPLY WITH FBC ACC. 603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES |
| | OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE |
| | OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM |
| | ABOVE THE FINISH FLOOR OR GROUND. /YOU SHOW THE BOTTOM |
| | OF THE MIRROR AT 24IN ABOVE THE FINISHED FLOOR IF THE |
| | LAVATORY IS SET AT 34IN TO THE RIM TO ACCOMMODATE KNEE |
| | A TOE CLEARANCE HOW CAN THE MIRROR BE SET AT 24IN |
| | PLEASE CLARIFY. PER WPB AMEND TP FBC 107.2.1 |
| | |
| | 2. DOOR TO BATHROOM SHALL COMPLY WITH FBC ACC 603.2.3 |
| | DOOR SWING. |
| | DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR |
| | CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE |
| | PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE. |
| | |
| | (3.) THE WATER CLOSET SHALL COMPLY |
| | 604.3.1 SIZE. |
| | CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| | (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| | WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED |
| | PERPENDICULAR FROM THE REAR WALL. |
| | PLEASE SHOW OVERALL DIMENSIONS OF BATHROOM TO SHOW |
| | COMPLIANCE |
| | |
| | (4) GRAB BARS SHALL COMPLY WITH FBC ACC 604.5.1 SIDE |
| | WALL. |
| | THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM) |
| | LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM |
| | THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM |
| | FROM THE REAR WALL. |
| | 604.5.2 REAR WALL. |
| | THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 |
| | INCHES (610 MM) MINIMUM ON THE OTHER |
| | |
| | (5) TOILET PAPER DISPENSER SHALL COMPLY WITH FBC ACC |
| | 604.7 DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| | DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48 |
| | INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND |
| | SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL |
| | NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES |
| | NOT ALLOW CONTINUOUS PAPER FLOW. |
| | |
| | (6) LAVATORY SHALL COMPLY WITH FBC ACC 606.2 CLEAR |
| | FLOOR SPACE. |
| | A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR |
| | A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | 606.3 HEIGHT. |
| | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| | (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | (8) PLEASE PROVIDE A WATER RISER DIAGRAM PER WPB AMEND. |
| | TO FBC SEC. 107.3.5.1.3(3) |
| | |
| | (9) A GREASE INTERCEPTOR IS REQUIRED FOR 3 COMP SINK |
| | AND SERVICE SINK. PER FBC PL SEC. 1003.1 WHERE |
| | REQUIRED. |
| | INTERCEPTORS AND SEPARATORS SHALL BE PROVIDED TO |
| | PREVENT THE DISCHARGE OF OIL, GREASE, SAND AND OTHER |
| | SUBSTANCES HARMFUL OR HAZARDOUS TO THE PUBLIC SEWER, |
| | THE PRIVATE SEWAGE SYSTEM OR THE SEWAGE TREATMENT PLANT |
| | OR PROCESSES. |
| | PROVIDE MANUFACTURE CALCULATIONS FOR GREASE INTERCEPTOR |
| | |
| | (10) IDENTIFY THE FIXTURE UPSTEAM OF THE WATER CLOSET. |
| | NO OTHER FIXTURES CAN TIE INTO THE WET VENT. THE 3 COMP |
| | SINK HAND SINK SHALL TIE IN DOWN STREAM OF BATHROOM |
| | GROUP. PER FBC PL SEC. 912.1 |
| | |
| | (11) THE 3 COMP. SINK SHALL BE INDIRECT WASTE. PER FBC |
| | PL SEC. 802.1 OR 802.1.8 |
| | |
| | (12) SHT. E-1 SHALL BE SIGNED AND SEALED PER FAC |
| | 61G15-23.001 |
| | |
| | 13. A SERVICE SINK IS REQUIRED .PER FBC PL TABLE 403.1 |
| | |
| | |
| | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND |
| | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON |
| | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |