| Date |
Text |
| 2016-04-20 07:34:13 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16040042 |
| | ADD: 1865 N. TAMARIND AVE. |
| | CONT: T. H. MOTTLEY |
| | TEL: 561-644-4081 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. APRIL 20/2016 |
| | ACTION: DENIED |
| | |
| | 1) SHEET S-1THE CODE DATA INDICATES THE OCCUANCY AS A |
| | A-2 OCCUPANCY BUT THE OCCUPANCY LOAD IS STATED AT 15. |
| | WITH THE OCCUPANT LOAD LESS THAN 50 OCCUPANTS THIS |
| | OCCUPANCY IS CLASSIFIED AS A BUSINESS OCCUPANCY. SEE |
| | 2014 FBC-B 303.1.1 SMALL BUILDINGS AND TENANT SPACES. A |
| | BUILDING OR TENANT SPACE USED FOR ASSEMBLY PURPOSES |
| | WITH AN OCCUPANT LOAD OF LESS THAN 50 PERSONS SHALL BE |
| | CLASSIFIED AS A GROUP B OCCUPANCY. |
| | |
| | 2) SHEET S-1 INDICATES THIS BUILDING TYPE AS A BUILDING |
| | TYPE III-B. PLEASE PROVIDE A SURVEY FOR THE DISTANCE |
| | FROM THE PROPERTY LINES CAN BE ESTABLISHED AND CODE |
| | COMPLIANCE WITH: |
| | 2014 FBC-B TABLE 602 & TABLE 705.8. |
| | |
| | 3) SHEET S-2 DOES NOT SHOW IF THE FRONT ENTRY IS AN |
| | ACCESSIBLE ENTRY, THAT THE ENTRY IS FLUSH WITH THE |
| | EXTERIOR AND THERE IS A THRESHOLD OF NOT MORE THAN 1/2 |
| | INCH IN HEIGHT. |
| | 2014 FBC-ACCESS. CODE 404.3.3 THRESHOLDS. THRESHOLDS |
| | AND CHANGES IN LEVEL AT DOORWAYS SHALL COMPLY WITH |
| | 404.2.5. |
| | 2014 FBC-ACCESS. CODE 404.2.5 THRESHOLDS. THRESHOLDS, |
| | IF PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH (13 MM) HIGH |
| | MAXIMUM. RAISED THRESHOLDS AND CHANGES IN LEVEL AT |
| | DOORWAYS SHALL COMPLY WITH 302 AND 303. EXCEPTION: |
| | EXISTING OR ALTERED THRESHOLDS 3/4 INCH (19 MM) HIGH |
| | MAXIMUM THAT HAVE A BEVELED EDGE ON EACH SIDE WITH A |
| | SLOPE NOT STEEPER THAN 1:2 SHALL NOT BE REQUIRED TO |
| | COMPLY WITH 404.2.5. |
| | |
| | 4) SHEET S-2 INDICATES NEW WINDOWS AND DOORS, NO |
| | PRODUCT APPROVALS WERE SUBMITTED PLAESE SHOW COMPLIANCE |
| | WITH: 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, IF INSTALLED, WALL |
| | LOUVERS, |
| | (D) IF INSTALLED, ROOFING PRODUCTS AND ASSEMBLIES, |
| | RURBS, INATAKE & EXHAUST ROOF TOP FANS, ROOF TOP RTUS |
| | (G) IF INSTALLED, PRE-ENGINEERED A/C STANDS |
| | |
| | |
| | 5) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 6) NOTICE COIL ROOF NAILS: ROOFING: NOTICE: EFFECTIVE |
| | APRIL 1/2016 THE REFERENCED MIAMI-DADE COUNTY |
| | ELECTROGALVANIZED FASTENERS LISTINGS ARE SUSPENDED: |
| | 11--1019.02 & 11-1019.03 BLUELINX CORP. |
| | 12-0423.06 CONTINENAL MATERIALS, INC. |
| | 15-1123.04 PRIME SOURCE BUILDING PRODUCTS, INC. |
| | 13-0530.01 SPECIALTY FASTENING SYSTEM |
| | 12-0423.03 & 12-0423.04 SUMMIT CONGLOMERATE, LLC |
| | 12-1205.11, 12-1205.13 & 13-05 & 13-0514.05 WEATHERPRO, |
| | LLC |
| | |
| | 7) FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS, |
| | DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL |
| | AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. |
| | 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| | AND BOTH SHORT- AND LONG-TERM |
| | MATERIAL PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED |
| | TO RESIST THE OVERTURNING EFFECTS CAUSED BY THE LATERAL |
| | FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR |
| | WIND LOADS? |
| | |
| | 8) DEPENDING ON THE PRODUCT APPROVALS FOR THE WINDOWS |
| | PRESSURES (MULLION) GIVEN MAYBE OR MAYBE NOT BE |
| | COMPLIANT FOR THE PRESSURES GIVEN ON SHEET S3. |
| | |
| | 9) 2014 FBC-B 1013.6 MECHANICAL EQUIPMENT. GUARDS SHALL |
| | BE PROVIDED WHERE APPLIANCES, EQUIPMENT, FANS, ROOF |
| | HATCH OPENINGS OR OTHER COMPONENTS THAT REQUIRE SERVICE |
| | ARE LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR |
| | OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN |
| | SIDE IS LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE |
| | FLOOR, ROOF OR GRADE BELOW. THE GUARD SHALL BE |
| | CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21 |
| | INCHES (533 MM) IN DIAMETER. THE GUARD SHALL EXTEND NOT |
| | LESS THAN 30 INCHES (762 MM) BEYOND EACH END OF SUCH |
| | APPLIANCE, EQUIPMENT, FAN OR COMPONENT. |
| | |
| | 10) 2014FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON |
| | ROOFS OR ELEVATED STRUCTURES. WHERE EQUIPMENT AND |
| | APPLIANCES REQUIRING ACCESS ARE INSTALLED ON ROOFS OR |
| | ELEVATED STRUCTURES AT A HEIGHT EXCEEDING 16 FEET (4877 |
| | MM), SUCH ACCESS SHALL BE PROVIDED BY A PERMANENT |
| | APPROVED MEANS OF ACCESS, THE EXTENT OF WHICH SHALL BE |
| | FROM GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND |
| | APPLIANCES? LEVEL SERVICE SPACE. SUCH ACCESS SHALL NOT |
| | REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 |
| | INCHES (762 MM) HIGH OR WALKING ON ROOFS HAVING A SLOPE |
| | GREATER THAN 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL |
| | (33-PERCENT SLOPE). |
| | |
| | 11) PLEASE PROVIDE RESTROOM ELEVATIONS TO SHOW CODE |
| | COMPLIANCE FOR ACCESSIBLE RESTROOM ELEMENTS, PROVIDE |
| | WIDTH AND HEIGHT ELEVATION INCOMPLIANCE WITH 2014 |
| | FBC-ACCESS. CHAPTER 6. |
| | |
| | 12) SHOW COMPLIANCE WITH: 2014 FBC-ACCESS. CODE 226.1 |
| | WHERE DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION |
| | OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING |
| | SPACES AND STANDING SPACES AT THE DINING SURFACES SHALL |
| | COMPLY WITH 902. |
| | |
| | 13) 2014 FBC-ACCESS. CODE 902.2 CLEAR FLOOR OR GROUND |
| | SPACE. A CLEAR FLOOR SPACE COMPLYING WITH 305 |
| | POSITIONED FOR A FORWARD APPROACH SHALL BE PROVIDED. |
| | KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE |
| | PROVIDED. |
| | |
| | 14) 2014 FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF |
| | DINING SURFACES AND WORK SURFACES SHALL BE 28 INCHES |
| | (710 MM) MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE |
| | THE FINISH FLOOR OR GROUND. |
| | |
| | 15) 2014 FBC-ACCESS. CODE 703.1SIGNS SHALL COMPLY WITH |
| | 703. RESTROOM SIGNAGE. WHERE BOTH VISUAL AND TACTILE |
| | CHARACTERS ARE REQUIRED, EITHER ONE SIGN WITH BOTH |
| | VISUAL AND TACTILE CHARACTERS, OR TWO SEPARATE SIGNS, |
| | ONE WITH VISUAL, AND ONE WITH TACTILE CHARACTERS, SHALL |
| | BE PROVIDED |
| | |
| | 16) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |