| Plan Review Notes For Permit 16040024 |
| Permit Number |
16040024 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-05 05:36:14 | 1) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF WHERE | | | THE SLAB WILL BE CUT. FBC 107.2.1. | | | 2) SUBMIT A SLAB REPAIR DETAIL SHOWING THE MINIMUM AND | | | MAXIMUM WIDTHS OF THE AREAS TO BE REPAIRED, THE SIZE OF | | | THE REBAR DOWELS TO BE INSTALLED, THE EMBEDMENT DEPTH | | | OF THE DOWELS INTO THE EXISTING SLAB, WHAT TYPE OF | | | EPXOY WILL BE USED IN THE EMBEDMENT OF THE DOWELS, THE | | | SPACING OF THE DOWELS ON CENTER, AND THE THICKNESS OF | | | THE SLAB. THIS INFORMATION IS REQUIRED TO ENSURE THE | | | INTEGRITY OF THE EXISTING SLAB WILL BE MAINTAINED. FBC | | | 107.2.1. | | | 3) THE SOIL SHALL BE TREATED FOR TEMITES PRIOR TO THE | | | POURING OF ANY CONCRETE. 2014 FBCR SEC. R 318. | | | 4) A MINIMUM 6 MIL VAPOR RETARDER SHALL BE PLACED OVER | | | THE SOIL PRIOR TO POURING ANY CONCRETE. 2014 FBCR | | | SEC.R506.2.3. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|