| 2016-04-05 07:03:50 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA RES BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | COMMENTS: |
| | |
| | 1. PLEASE PROVIDE UPDATED CODE REFERENCES AS LISTED |
| | ABOVE. NEC 2008 AS SHOWN NEEDS TO BE REVISED. |
| | 2. SHOW A SMOKE DETECTOR AT THE LANDING AREA OF STAIRS. |
| | FBC RES 314 |
| | 3. GENERAL NOTE TO INDICATED REQUIRED SEPARATE PERMITS |
| | FOR LOW VOLTAGE SYSTEMS AND POOL. |
| | 4. LABEL MAIN DISCONNECTS 1 OF 3, 2 OF 3 AND 3 OF 3. |
| | FBC RES E3601 |
| | 5. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE |
| | PER FBC RES E3609.3 |
| | 6. CLARIFY WHY GROUNDING ELECTRODE CONDUCTORS ARE SHOWN |
| | AT EACH INDIVIDUAL PANEL BOARDS AND NOT TO COMMON |
| | ELECTRODE AT THE SERVICE. |
| | 7. PLEASE SHOW THE FEEDER CONDUCTOR SIZES AND EQUIPMENT |
| | GROUNDING CONDUCTOR REQUIRED WITH THESE FEEDERS. FBC |
| | 107.3.5 |
| | 8. PROVIDE A NOTE AT THE ISLAND COUNTERTOP TO COMPLY |
| | WITH FBC RES E3901.4.4 SEPARATE SPACES. A NOTE WILL |
| | SUFFICE. |
| | 9. SHOW ON DRAWING THE RECEPTACLE OUTLETS REQUIRED FOR |
| | WALL SPACE AT LIVING ROOM FOR WALL OVER 2FT . TO COMPLY |
| | WITH FBC RES- SEC E3901 2.1 AND 2.2 |
| | 10. SHOW ON DRAWING THE RECEPTACLE OUTLETS REQUIRED FOR |
| | WALL SPACE LEFT OF SLIDING GLASS DOOR AREA OF THE |
| | FAMILY ROOM. TO COMPLY WITH FBC RES- SEC E3901 2.1 AND |
| | 2.2 |
| | 11. PROVIDE AIC CALCULATIONS FOR NEW SERVICE SHOWN AND |
| | LABEL SERVICE EQUIPMENT AND PANEL BOARDS WITH AIC |
| | RATINGS. FBC 107.3.5 |
| | 12. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY |
| | QUESTIONS OR CONCERNS. |
| | |
| | VALENTINO PEREZ |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |