Plan Review Notes
Plan Review Notes For Permit 16031485
Permit Number 16031485
Review Stop E
Sequence Number 1
Notes
Date Text
2016-04-05 07:03:50INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE PROVIDE UPDATED CODE REFERENCES AS LISTED
 ABOVE. NEC 2008 AS SHOWN NEEDS TO BE REVISED.
 2. SHOW A SMOKE DETECTOR AT THE LANDING AREA OF STAIRS.
 FBC RES 314
 3. GENERAL NOTE TO INDICATED REQUIRED SEPARATE PERMITS
 FOR LOW VOLTAGE SYSTEMS AND POOL.
 4. LABEL MAIN DISCONNECTS 1 OF 3, 2 OF 3 AND 3 OF 3.
 FBC RES E3601
 5. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE
 PER FBC RES E3609.3
 6. CLARIFY WHY GROUNDING ELECTRODE CONDUCTORS ARE SHOWN
 AT EACH INDIVIDUAL PANEL BOARDS AND NOT TO COMMON
 ELECTRODE AT THE SERVICE.
 7. PLEASE SHOW THE FEEDER CONDUCTOR SIZES AND EQUIPMENT
 GROUNDING CONDUCTOR REQUIRED WITH THESE FEEDERS. FBC
 107.3.5
 8. PROVIDE A NOTE AT THE ISLAND COUNTERTOP TO COMPLY
 WITH FBC RES E3901.4.4 SEPARATE SPACES. A NOTE WILL
 SUFFICE.
 9. SHOW ON DRAWING THE RECEPTACLE OUTLETS REQUIRED FOR
 WALL SPACE AT LIVING ROOM FOR WALL OVER 2FT . TO COMPLY
 WITH FBC RES- SEC E3901 2.1 AND 2.2
 10. SHOW ON DRAWING THE RECEPTACLE OUTLETS REQUIRED FOR
 WALL SPACE LEFT OF SLIDING GLASS DOOR AREA OF THE
 FAMILY ROOM. TO COMPLY WITH FBC RES- SEC E3901 2.1 AND
 2.2
 11. PROVIDE AIC CALCULATIONS FOR NEW SERVICE SHOWN AND
 LABEL SERVICE EQUIPMENT AND PANEL BOARDS WITH AIC
 RATINGS. FBC 107.3.5
 12. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  