| 2016-04-26 11:06:43 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16031458 | | | 4/26/16 | | | | | | 1) PROVIDE A COMMISSIONING PLAN IN COMPLIANCE WITH | | | SECTION C408.2 AND C408.2.3.1 FBC-14 ENERGY | | | CONSERVATION | | | 2) INDICATE THE CLEARANCE HEIGHT FROM THE FINISHED ROOF | | | SURFACE TO THE BOTTOM OF THE SUPPORT STRUCTURE- TABLE | | | 1509.6.5 FBC-14 BUILDING. | | | 3) PROVIDE ENGINEERED ATTACHMENT DETAILS FOR MOUNTING | | | THE CHILLERS TO THE NEW AND RE-FURBISHED SUPPORT | | | PLATFORM- SECTION 301.15 FBC-14 MECHANICAL. | | | 4) PROVIDE GUARD AND HANDRAIL DETAILS FOR THE EQUIPMENT | | | PLATFORMS- SECTIONS 1012 & 1013 FBC-14 BUILDING. | | | 4) PROVIDE A SITE PLAN SHOWING THE TEMPORARY LOCATION | | | OF OF THE CHILLER ON THE NORTH GRADE AND INCLUDE | | | DETAILS FOR PROTECTION OF THE EQUIPMENT AND COMPONENTS | | | FROM VEHICULAR IMPACT, AND SAFE GUARDS TO PROTECT THE | | | PUBLIC- SECTIONS 303.4 FBC-14 MECHANICAL, AND 3301.2 | | | FBC-14 BUILDING. | | | 5) PROVIDE A TEMPORARY HYDRONIC PIPING PLAN INDICATING | | | THE PIPING RUNS, PIPE ANCHORAGE AND SUPPORT, AND | | | PROTECTIONS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|