| Plan Review Notes For Permit 16031454 |
| Permit Number |
16031454 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-04-25 05:37:52 | 1) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014 | | | FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G | | | 2407. 2ND REQUEST. | | | 2) THE PLANS SHOW PE PIPING BEING INSTALLED INSIDE THE | | | STRUCTURE. PE PIPING SHALL ONLY BE INSTALLED OUTSIDE | | | UNDERGROUND PER 2014 FBCR SEC.G2415.17.1 | | | 3) THE MAXIMUM BTU LOAD ON A 3/4" SCH.40 METALLIC PIPE | | | AT 80 FEET IS 117,000 BTU'S. THE PLANS SHOW A MAXIMUM | | | BTU LOAD OF 157,000 BTU'S. THE SYSTEM IS UNDERSIZED. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|