Plan Review Notes
Plan Review Notes For Permit 16031454
Permit Number 16031454
Review Stop G
Sequence Number 2
Notes
Date Text
2016-04-25 05:37:521) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G
 2407. 2ND REQUEST.
 2) THE PLANS SHOW PE PIPING BEING INSTALLED INSIDE THE
 STRUCTURE. PE PIPING SHALL ONLY BE INSTALLED OUTSIDE
 UNDERGROUND PER 2014 FBCR SEC.G2415.17.1
 3) THE MAXIMUM BTU LOAD ON A 3/4" SCH.40 METALLIC PIPE
 AT 80 FEET IS 117,000 BTU'S. THE PLANS SHOW A MAXIMUM
 BTU LOAD OF 157,000 BTU'S. THE SYSTEM IS UNDERSIZED.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  