Plan Review Notes
Plan Review Notes For Permit 16031436
Permit Number 16031436
Review Stop P
Sequence Number 1
Notes
Date Text
2016-04-11 09:10:41PLUMBING COMMENTS:
  
 1.THE TUB AND THE SHOWER IN THE MASTER BATHROOM ARE NOT
 VENTED.
 SHALL COMPLY WITH FBC RES. SEC. P3101.2.1
  
 2.THE BACK TO BACK WATER CLOSETS IN THE MASTER BATHROOM
 AND POWDER ROOM BATH SHALL NOT BE INSTALLED ON A DOUBLE
 SANITARY TEE THE WAY YOU HAVE IT DRAWN ON RISER.
 PER FBC RES.SEC. P3005.1.1
  
 3. IT APPEARS THAT YOU HAVE THE BUILDING DRAIN RUNNING
 PARALLEL UNDER THE FOOTER THIS IS NOT PERMITTED, IT
 ALSO CREATES OTHER PROBLEMS WITH VENTING AND
 CONNECTIONS OF THE PLUMBING SYSTEM.
 PER FBC RES. SEC. R403.1
  
 4.WHAT IS THE 12"X11/2" RECESSED WATER STOP SHT.S1
 PLEASE CLARIFY.
 PER WPB AMEND.TO FBC 107.2.1
  
 5. A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW FOR
 THE POOL.
 PER WPB UTILITIES DEPT CROSS CONNECTION MANUAL SEC I
 PG. 19
  
  
  
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  