2016-04-04 07:49:21INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE SHOW ON DRAWING THE RECEPTACLE OUTLETS
 REQUIRED FOR WALL SPACE SLIDING GLASS DOOR AREA OF THE
 FAMILY ROOM. CLARIFY LAYOUT TO COMPLY WITH FBC RES- SEC
 E3901 2.1 AND 2.2
 2. PROVIDE A NOTE TO COMPLY WITH TAMPER RESISTANT
 RECEPTACLE PER FBC RES-E4002.14
 3. PROVIDE AIC CALCULATIONS FOR NEW SERVICE SHOWN AND
 LABEL SERVICE EQUIPMENT AND PANEL BOARDS WITH AIC
 RATINGS. FBC 107.3.5
 4. LABEL GDO RECEPTACLE IN GARAGE TO BE GFCI PROTECTED.
 FBC RES E3902.2
 5. RECEPTACLE REQUIRED AT THE REAR OF DWELLING NO MORE
 THAN 6FT 6INCHES ABOVE GRADE PER FBC RES E3901.7
 6. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  