| 2016-05-02 17:11:32 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) WOOD CONSTRUCTION NOTE #2 ON SHEET A-1 REFERENCES |
| | CHAPTER 23 OF THE 2010 FBC. THE CORRECT REFERENCE IS |
| | CHAPTER 6 OF THE 2014 FBC RESIDENTIAL. |
| | |
| | 2) THE DOOR FROM THE GARAGE TO THE RESIDENCE IS |
| | REQUIRED TO HAVE A SELF-CLOSING DEVICE. FBC R302.5.1 |
| | |
| | 3) THERE IS A DISCREPANCY BETWEEN THE PLANS AND THE |
| | ENERGY COMPLIANCE FORMS. THE TYPICAL WALL SECTION ON |
| | SHEET A-3 SPECIFIES R-30 INSULATION AND SCREEN VENTS IN |
| | THE SOFFIT. THE ENERGY FORMS HAVE R-20 INSULATION AND |
| | AN UN-VENTED ATTIC. CLARIFY. FBC 107.2.1 |
| | |
| | 4) SPECIFY THE REQUIRED DESIGN PRESSURES FOR ROOF ZONES |
| | 1, 2 & 3 FOR THE 5/12 SLOPE ROOF ON THE PLANS. FBC |
| | R301.2.1 |
| | |
| | 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| | THAT HAVE BEEN REVIEWED AND "APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD". PROVIDE TWO COMPLETE PRODUCT |
| | APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION |
| | INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF |
| | THE SINGLE HUNG WINDOWS, STRUCTURAL MULLIONS, SLIDING |
| | GLASS DOORS, ENTRY DOOR AND EXTERIOR OUTSWING DOOR AT |
| | THE GARAGE. |
| | |
| | THE FOLLOWING IS A LINK TO THE MIAMI - DADE PRODUCT |
| | APPROVAL WEBSITE. |
| | HTTP://WWW.MIAMIDADE.GOV/BUILDING/PC-SEARCH_APP.ASP |
| | |
| | THE FOLLOWING IS A LINK TO THE FLORIDA PRODUCT APPROVAL |
| | WEBSITE. |
| | HTTPS://FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX |
| | |
| | 6) THE PRODUCT APPROVAL FOR THE SECTIONAL GARAGE DOOR |
| | HAS MAXIMUM DESIGN PRESSURES OF +36.0, -44.0 PSF AND |
| | THE PLAN (SHEET A-2) REQUIRES |
| | +49.1, -54.0 PSF. |
| | |
| | 7) SPECIFY WHICH ONE OF THE ROOFING UNDERLAYMENTS |
| | LISTED IN THE TARCO PRODUCT APPROVAL (FL10450) WILL BE |
| | USED. |
| | |
| | 8) VALUATION OF WORK WAS INCREASED TO $336,528.00. FBC |
| | 109.31 |
| | |
| | IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A |
| | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |
| | RE-SUBMITTAL PROCEDURE |
| | |
| | YOU WILL BE REQUIRED TO FILL OUT A RE-SUBMITTAL FORM TO |
| | BE SUBMITTED WITH THE CORRECTED PLANS AND/OR OTHER |
| | DOCUMENTS. THE PERMIT CLERK WILL RETRIEVE THE DENIED |
| | APPLICATION, PLANS AND OTHER DOCUMENTS FOR YOU. YOU ARE |
| | REQUIRED TO REMOVE THE OLD PLAN SHEETS THAT HAVE BEEN |
| | CORRECTED AND REPLACE THEM WITH THE NEW ONES. THE CLERK |
| | WILL PROVIDE YOU WITH A STAPLE REMOVER AND A STAPLER. |
| | ONE SET OF THE OLD PLAN SHEETS THAT HAVE BEEN REMOVED |
| | SHALL BE MARKED AS VOIDED AND RESUBMITTED ALONG WITH |
| | THE TWO (OR MORE) SETS THAT CONTAIN THE CORRECTED |
| | SHEETS. IF THERE ARE ANY SHEETS THAT HAVE BEEN STAMPED |
| | FOR COUNTY IMPACT FEES, HOA APPROVAL STAMPS OR OTHERS, |
| | RESUBMIT THOSE SHEETS. |
| | IF ALL OF THE PLAN SHEETS HAVE BEEN CORRECTED, THEN TWO |
| | (OR MORE) SETS OF THE NEW PLANS AND ANY OTHER DOCUMENTS |
| | SHALL BE SUBMITTED. |
| | |