| 2016-03-30 18:30:28 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE SYSTEM NUMBER IS NOT SPECIFIED ON THE | | | CERTAINTEED PRODUCT APPROVAL. FBC 107.2.1 | | | 2) THE ENHANCED FASTENING FOR THE BASE SHEET IS NOT | | | SPECIFIED ON THE CERTAINTEED PRODUCT APPROVAL. FBC | | | 107.2.1 | | | 3) THE BASE SHEET FOR ONE SYSTEM IS HI-LITED FOR ONE | | | ROOF ASSEMBLY AND THE CAP SHEET FOR A DIFFERENT | | | ASSEMBLY IS HI-LITED. THE TWO PRODUCTS ARE NOT | | | INTERCHANGABLE. FBC R904.2 |
|