2016-04-05 12:38:22 | PERMIT #16031416 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| APPROVED PROVISO: |
| |
| 1) PLEASE NOTE THAT FIRE ALARM DEVICES IN THIS SPACE |
| WAS INSTALLED FOR THE WHITE BOX, ONLY. ADDITIONAL |
| DEVICES MAY BE REQUIRED TO MEET FIRE CODE REQUIREMENTS |
| FOR OCCUPANCY TYPE. SUB-PERMITS REQUIRED FOR ALL WORK |
| DONE RELATED TO THE FIRE ALARM AND SPRINKLER SYSTEM. |
| |
| 2) FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| BE SUBMITTED BY EMAIL ([email protected]) |
| ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND |
| APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT |
| 500 NORTH DIXIE HIGHWAY. |
| |
| 3) ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A |
| LOCK/UNLOCK INDICATOR. |
| |
| 4) EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED |
| WITH SIGNS OR STENCILING READING FIRE BARRIER-PROTECT |
| ALL OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN |
| HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE |
| SPACED NOT MORE THAN 15 FEET ON CENTER. |
| |
| 5) PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN |
| STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE |
| MAINTAINED AT ALL TIMES. |
| |
| 6) SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO |
| THE FIRE ALARM AND SPRINKLER SYSTEM. |
| |
| 7) WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT |
| SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED |
| AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE |
| MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM |
| SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD |
| INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY |
| BE NEEDED. |
| |
| |